Jandy LD Скачать руководство пользователя страница 8

Page 6

WATERPIK TECHNOLOGIES INC.

7.

Disconnect the heater and its individual shutoff

valve from the gas supply system during pressure

testing of the system at pressures higher than 1/2

pounds per square inch (psi) (3.45 kilopascals

[kPa]). If the test pressure is equal to or less than

1/2 psi (3.45 kPa), close the manual shutoff valve

on the heater during the piping pressure test.

Caution

Permanent damage to the gas valve will occur

if the following procedures are not followed.

8.

If the gas supply pressure is less than required,

check for undersized pipe between the meter and

the heater, a restrictive fitting, or an undersized

gas meter. Gas supply pressures to the heater are

listed in Table 4.

NOTE:

 The maximum inlet gas pressure must

not exceed the specified value. The minimum  value

listed is for the purpose of input adjustment.  Refer to

Table 4.

9.

Before operating the heater, test the complete gas

supply system and all connections for leaks using

a soap solution. Do not use an open flame.

Caution

Some leak test solutions (including soap and

water) may cause corrosion or stress cracking.

Rinse the piping with water after testing.

2E-2. Special Precautions for Propane

Gas

Liquefied petroleum (LP) gas is heavier than air.

Therefore, do not install pool heaters using LP gas in

pits or locations where gas might collect. Locate

heaters a safe distance from LP gas storage and filling

equipment. Consult local codes and fire protection

authorities about specific installation restrictions.

5.

Install a sediment trap (drip leg) ahead of the gas

controls (see Figure 5). Fit the trap with a

threaded cap which can be removed for cleaning.

6.

Install a manual gas shutoff valve for service and

safety. Do not use a restrictive gas cock. DO

NOT USE FLEXIBLE GAS PIPING.

2F. Electrical Wiring

Caution

Label all wires prior to disconnection when

servicing controls. Wiring errors can cause

improper and dangerous operation.

Verify proper operation after servicing.

Attention

Au moment de l'entretien des commandes,

étiquetez tous les fils avant de les débrancher.

Des erreurs de câblage peuvent entraîner un

fonctionnement inadéquat et dangereux.

2F-1. General Information (LD Only)

Wiring connections must be made exactly as

shown in the wiring diagram found on the inside of the

heater (see Figures 6 and 7 for typical examples) . The

heater must include a definite means of grounding.

There is a bonding lug on the right side of the heater,

where a bond wire must be attached.

The heater comes factory-wired intended for

use with 240 Volt, 60 Hz AC field electrical supply.

To use 120 Volt, 60 Hz AC requires rewiring of the

heater. 

This should be done by a certified electrician

only, as with all wiring. To wire the heater for 120

Volt, 60 Hz AC, follow the alternate 120V wiring

method depicted in Figure 6. Additionally, the ignition

control module must be rewired. The wire from the

terminal marked IGN/240 must be removed from that

terminal and placed on the terminal marked IGN/120.

Electrical wiring must be in accordance with the

latest edition of the National Electric Code (NEC),

ANSI/National Fire Protection Association (NFPA)

70, unless local code requirements indicate otherwise.

To wire the Laars Lite 2 model LD heater to a

120V or 240V /60 Hertz (Hz) electrical source:

1.

Remove the screw located to the lower right side

of  the transformer and open the hinged cover of

the wiring enclosure.

2.

Connect the wires from the power source to the

leads on the right side of the heater in the space

behind the ignition control (see Figure 8). Be sure

to follow the wiring diagram on page 7 to config-

ure the transformer for the correct input voltage.

3.

Attach the ground wire to the green ground screw

located on the back panel of the wiring enclosure.

4.

Close the cover of the wiring enclosure and

replace the screw to hold it in place.

5.

Connect a bonding wire (8 ga copper) to the

bonding lug on the right side of the heater.

NOTE: 

No external junction box is required.

Table 4.  Gas Supply Pressure Requirements

Supply Pressure

Natural Gas

Propane Gas

Water Column

in. (mm)

in.

(mm)

Minimum

5.5 (140)

10.0 (254)

Maximum

10.0 (254)

14.0 (356)

Содержание LD

Страница 1: ...y damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any...

Страница 2: ...9 2G 2 Reversible Water Connections 10 2G 3 Valve Installation 12 2G 4 Chlorinators Ozone Generators and Sanitizing Chemicals 12 2G4a Water Chemistry 13 2G 5 Pressure Relief Valve 13 2G 6 Adjusting t...

Страница 3: ...g with the latest edition of the Standard for Notes 1 In Canada derate BTU Hr input and output 10 percent for altitudes of 2 000 to 4 500 feet 609 to 1372 m above sea level No derating necessary up to...

Страница 4: ...the proper perfor mance and application of Waterpik Laars products For technical support call 415 382 8220 extension 260 SECTION 2 Installation Instructions 2A General Information Install the Laars L...

Страница 5: ...ate leakage If this is not possible provide a suitable drain pan to catch and divert any leakage The pan must not block natural flow of air around the heater Locate the heater so the clearances from c...

Страница 6: ...r at least 3 Figure 4 Non Combustible Platform Notes 1 Blocks must provide solid base and be braced so they cannot slip out of place 2 Air openings in blocks must be arranged to provide unrestricted o...

Страница 7: ...2 Check the rating plate to make sure the heater is fitted for the type of gas being used Waterpik Laars heaters as shipped from the factory are certified to operate at an altitude of 0 to 3000 feet 0...

Страница 8: ...ttention Au moment de l entretien des commandes tiquetez tous les fils avant de les d brancher Des erreurs de c blage peuvent entra ner un fonctionnement inad quat et dangereux 2F 1 General Informatio...

Страница 9: ...gram b Schematic Diagram WIRING SHOWN AS SHALL USE APPLIANCE WIRING MATERIAL RATED AT 200 C O HSI IGNITION WIRE FACTORY WIRED 120 V 240 V FIELD WIRED 120V 240V FACTORY WIRED 24 V IF ORIGINAL WIRE SUPP...

Страница 10: ...de power to the heater from the high voltage side of the time clock Doing so may cause damage to the heater or surrounding plumbing 0 92 7 7 5 5 1 5 0 Y Connection Diagram BK TH PP Y Y W PP TH Pilot G...

Страница 11: ...connected by removing the jumper wire on the terminal block located in the control compartment see Figure 6 and connecting the two wires from the remote to the two terminals on the terminal block This...

Страница 12: ...side It could be necessary or helpful to switch the connections to the left side to improve access for installation and service Perform this modification before installing the heater using the follow...

Страница 13: ...changer 10 Unscrew the brass compression fitting securing the pressure switch to the inlet outlet header Remove tube from header and gently bend it out of the way 11 Loosenthescrewsecuringthetemperatu...

Страница 14: ...ater damage caused by exces sive chemicals or improper ozonization is not covered by the Waterpik Laars warranty Be sure to adhere to thefollowing When ozone is injected upstream of the heater install...

Страница 15: ...The back pressure could be too low to trigger the pressure switch If this happens it may be necessary to install a directional fitting or elbows where the return line enters the pool This will increas...

Страница 16: ...ains off This allows water from the pool to reach the heater 7 Record the temperature indicated by the ther mometer cold water 8 Turn the heater ON following the lighting in structions found on the in...

Страница 17: ...ve thermometer and Pete s plug d Replace the drain plug 2G 9 Adjusting the Manual Bypass Valve After the manual bypass valve is installed use the following procedures to adjust the bypass valve 1 Clea...

Страница 18: ...ts off the top of the heater Blocking air flow could damage the heater and may void the warranty WARNING Vent pipes drafthoods and heater tops get hot These surfaces can cause serious burns Do not tou...

Страница 19: ...to the appliance if service is to be performed 3 Turn gas control knob clockwise to OFF 4 Replace control access panel A This appliance does not have a pilot light It is equipped with an ignition dev...

Страница 20: ...he knob will not push in or turn by hand don t try to repair it Call a qualified service techni cian Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part...

Страница 21: ...only going to be used occasionally turn the temperature control down to the MIN setting This prevents the pool from water from becoming chilled and minimizes the time re quired to raise the pool wate...

Страница 22: ...temperature of 98 6 F 37 C Symptoms include dizziness fainting drowsiness lethargy and an increase in the internal body temperature The effects of hyperthermia include Lack of awareness of impending h...

Страница 23: ...ose or broken wires and terminal connections 2 Verify pressure switch operation by cycling the spa pump on and off a few times The heater should go off immediately after the pump stops 3 Inspect the e...

Страница 24: ...own All 10480000 VENT SYSTEM 59 Top Enclosure 125 400 R0343401 05 60 Top Filler Plate US Only 125 400 R0343701 05 61 Rainshield Kit US Only 125 400 R0318301 05 61 Rainshield Kit Canada Only 125 400 R0...

Страница 25: ...NER TRAY LDSHOWN SEE NEXT PAGE FOR DETAIL 50 51 52 53 54 66 60 59 61 62 65 UNITED STATES CANADA UNITED STATES CANADA UNITED STATES 82 82 85 85 101 102 103 104 105 106 107 108 HEAT EXCHANGER SEE NEXT P...

Страница 26: ...6 14 8 5 2 1 4 34 16 18 70 98 96 97 75 72 75 74 38 32 95 86 85 49 48 69 47 44 45 80 77 79 78 81 90 93 88 94 91 39 30 31 43 76 87 23 22 36 28 34 26 33 25 LD SHOWN 29 27 35 3 12 LG SHOWN 19 24 13 20 LG...

Страница 27: ...Model LG LD Pool and Spa Heater Page 25 NOTES...

Страница 28: ...thorized parts or accessories in conjunction with the product s 8 Chemical contamination of combustion air or improper use of sanitizing chemicals such as introducing sanitizing chemicals upstream of...

Отзывы: