HB Products HBLT-A1 Liquid Level Transmitters 

Section 9 

 

Publication 9-86 

Issue 1 : 10/22 

 

Page 7 of 10 

6.1. 

Selecting the Refrigerant 

The liquid level transmitter is supplied factory set for use with R717 

(ammonia) refrigerant.  If this refrigerant is used there is no need to 

change this setting.  For other refrigerants, or if the transmitter housing 

electronics have been replaced, proceeds as follows: 
(a)  Arrange to measure the 4 to 20 mA output signal. 
(b)  Disconnect the power supply by unplugging the DIN plug from the 

transmitter housing. 

(c) 

Press the calibration pushbutton and keep it pressed while 

restoring the power supply (reinstate the DIN plug).  Release the 

pushbutton. 

NOTE: If the power supply is restored before the 

calibration pushbutton is pressed, the signal damping 

will be changed; refer to 6.2. 

(d)  Observe the green LED flashing, at the same time measure the 

4 to 20 mA output signal; refer to Table 2. 

 

Green LED Number of Flashes 

4 to 20 mA Output Signal 

1

Refrigerant 

1 flash 

5 mA 

R717 (ammonia) (factory setting) 

2 flashes 

6 mA 

R22 and R507A 

3 flashes 

7 mA 

R404A 

4 flashes 

8 mA 

R134a 

5 flashes 

9 mA 

R744 (CO

2

1

For refrigerants not listed, contact J & E Hall International. 

Table 2 Refrigerant Settings 

 
(e)  Press and release the pushbutton to step down through the list 

until the number of LED flashes and the output signal correspond 

to the required refrigerant. 
When the output current corresponds to the required 

refrigerant, wait 10 seconds until the green LED is constantly 

lit (not flashing).  This indicates that the required refrigerant 

has been selected. 

(f) 

Leave change of refrigerant mode by disconnecting the power 

supply to the transmitter (unplug the DIN plug from the transmitter 

housing). 

(g)  Reinstate the power supply. 

6.2. 

Signal Damping 

The signal damping setting range is 1 to 120 seconds, factory setting 15 

seconds.  To change the signal damping proceed as follows: 
(a)  Disconnect the power supply by unplugging the DIN plug from the 

transmitter housing.  Restore the power supply (reinstate the DIN 

plug). 

(b)  Press and release the calibration pushbutton.  Each press and 

release increases the signal damping by 1 second from 1 second 

up to a maximum of 120 seconds. 
For example, to set signal damping to 37 seconds, press 

and release the pushbutton 37 times. 

(c) 

10 seconds after the last press and release, the damping value is 

saved to memory and the green LED will start flashing. 
If the damping is set too high, repeat the procedure from 

step (a). 

Содержание HBLT-A1

Страница 1: ...ximum Calibration When the Maximum Liquid Level is Different From 20 mA 9 6 4 Restore Factory Default Settings 9 6 5 LED Indication 9 7 Maintenance 10 8 Faults and Remedies 10 9 Spare Parts 10 10 Safe...

Страница 2: ...ons including recommended precautions are not followed WARNING This indicates a hazard with a medium level of risk which if not avoided will result in death or serious injury if instructions including...

Страница 3: ...gerants R22 R134a R404A R507A R717 ammonia R718 water R744 CO2 Electrical Voltage 24 V ac dv 10 50 60 Hz Power 1 5 W Maximum load resistance 500 max Connection Plug 4 pins DIN 43650 Cable Wire Size 3...

Страница 4: ...m 1 BSP HBLT A1 15 3U HBLT A1B 15 3U 15 3 in NPT HBLT A1 5 HBLT A1B 5 500 mm HBLT A1 19 2U HBLT A1B 19 2U 19 2 in HBLT A1 8 HBLT A1B 8 800 mm HBLT A1 23 1U HBLT A1B 23 1U 23 1 in HBLT A1 10 HBLT A1B 1...

Страница 5: ...n to the change in liquid level It is not necessary to break into the system to replace the transmitter housing electronics This item can be separated from the transmitter rod by hand 5 Installation 5...

Страница 6: ...ommissioning WARNING The pressure and temperature parameters detailed in Table 1 must NOT be exceeded when pressure testing the plant When the plant is charged with refrigerant for the first time leav...

Страница 7: ...rigerants not listed contact J E Hall International Table 2 Refrigerant Settings e Press and release the pushbutton to step down through the list until the number of LED flashes and the output signal...

Страница 8: ...lease the pushbutton once within the next 10 seconds NOTE The level switch will return to normal operation if the pushbutton is not pressed within 10 seconds After a few seconds the green LED starts t...

Страница 9: ...0 5 mA from the desired point f Repeat steps c and d Each repeat will decrease the output signal by approximately 0 05 mA 10 seconds after the last repeat the green LED starts to flash The output now...

Страница 10: ...spond to the actual liquid level Wrong refrigerant selected Select correct refrigerant refer to 6 1 Level transmitter not calibrated or incorrect calibration Calibrate level transmitter refer to 6 3 I...