background image

 

HB Products HBLT-A1 Liquid Level Transmitters 

Publication 9-86 

 

Section 9 

Page 10 of 10 

 

Issue 1 : 10/22 

7. 

Maintenance 

No routine maintenance is required other than periodically checking that 

the level indicated corresponds to the liquid level within the vessel. 
If the system uses R717 (ammonia) refrigerant, oil may tend to collect at 

the bottom of the level column.  The HBLT-A1 is less susceptible to oil 

logging than other designs of level transmitter, however, if it is suspected 

that oil accumulation might be interfering with the correct operation of the 

transmitter, drain off the oil using the apparatus and method illustrated 

and described in Pumping Down, Recovering Ammonia Refrigerant 

Charge in publication 5-20 in Section 5. 

8. 

Faults and Remedies 

Some of the more common fault conditions are given in Table 3. 
 

Fault 

Probable Cause 

Remedy 

No function, green LED not lit. 

No power supply or power supply incorrect, faulty 

wiring/plug. 

Check power supply is available, supply polarity and 

voltage is correct.  Check wiring continuity and plug 

connections. 

Level transmitter electronic defective. 

Replace electronics. 

No 4 to 20 mA output signal, green LED flashes 

rapidly. 

Faulty wiring/plug 

Check supply polarity.  Check wiring continuity and 

plug connections. 

4 to 20 mA output signal does not correspond to the 

actual liquid level 

Wrong refrigerant selected. 

Select correct refrigerant; refer to 6.1. 

Level transmitter not calibrated or incorrect 

calibration. 

Calibrate level transmitter; refer to 6.3.  If calibration 

has been carried out incorrectly, restore factory 

default settings before recalibrating. 

4 to 20 mA output signal is low or erratic 

Oil accumulation in the standpipe. 

Drain off the oil; refer to 7. Maintenance. 

After supplying power to the level transmitter, there is 

a long delay before the 4 to 20 mA output signal is 

recognised and updated 

Minimum/maximum calibration has been carried 

out many times. 

When power is applied to the level transmitter the 

LED will flash rapidly as many times as the 

transmitter has been calibrated during its lifetime.  

The 4 to 20 mA output signal is recognised and 

updated as soon as the flashing changes from rapid 

to slow flashing. 

Table 3 Faults and Remedies 

 

9. 

Spare Parts 

Obtain spare parts from the address below: 

J & E Hall International       Telephone: +44 (0) 1332-253400 

Hansard Gate, 

         Fax: +44 (0) 1332-371061 

West Meadows, 

         Email: [email protected] 

Derby, 

 

         Website: www.jehall.com 

DE21 6JN 

England 

When ordering always quote the J & E Hall International contract number 

and the component serial number (if available). 

10.  Safe Disposal, End-of-life (EOL) 

At the end of the level transmitter's working life, it should not be classed 

as domestic waste but be disposed of separately by a registered 

recycling company according to local and currently valid legislation. 
 
 

 

Содержание HBLT-A1

Страница 1: ...ximum Calibration When the Maximum Liquid Level is Different From 20 mA 9 6 4 Restore Factory Default Settings 9 6 5 LED Indication 9 7 Maintenance 10 8 Faults and Remedies 10 9 Spare Parts 10 10 Safe...

Страница 2: ...ons including recommended precautions are not followed WARNING This indicates a hazard with a medium level of risk which if not avoided will result in death or serious injury if instructions including...

Страница 3: ...gerants R22 R134a R404A R507A R717 ammonia R718 water R744 CO2 Electrical Voltage 24 V ac dv 10 50 60 Hz Power 1 5 W Maximum load resistance 500 max Connection Plug 4 pins DIN 43650 Cable Wire Size 3...

Страница 4: ...m 1 BSP HBLT A1 15 3U HBLT A1B 15 3U 15 3 in NPT HBLT A1 5 HBLT A1B 5 500 mm HBLT A1 19 2U HBLT A1B 19 2U 19 2 in HBLT A1 8 HBLT A1B 8 800 mm HBLT A1 23 1U HBLT A1B 23 1U 23 1 in HBLT A1 10 HBLT A1B 1...

Страница 5: ...n to the change in liquid level It is not necessary to break into the system to replace the transmitter housing electronics This item can be separated from the transmitter rod by hand 5 Installation 5...

Страница 6: ...ommissioning WARNING The pressure and temperature parameters detailed in Table 1 must NOT be exceeded when pressure testing the plant When the plant is charged with refrigerant for the first time leav...

Страница 7: ...rigerants not listed contact J E Hall International Table 2 Refrigerant Settings e Press and release the pushbutton to step down through the list until the number of LED flashes and the output signal...

Страница 8: ...lease the pushbutton once within the next 10 seconds NOTE The level switch will return to normal operation if the pushbutton is not pressed within 10 seconds After a few seconds the green LED starts t...

Страница 9: ...0 5 mA from the desired point f Repeat steps c and d Each repeat will decrease the output signal by approximately 0 05 mA 10 seconds after the last repeat the green LED starts to flash The output now...

Страница 10: ...spond to the actual liquid level Wrong refrigerant selected Select correct refrigerant refer to 6 1 Level transmitter not calibrated or incorrect calibration Calibrate level transmitter refer to 6 3 I...

Отзывы: