60
If s=A.... is read, since A = 2 + 8, it is inferred that:
1=system temperature is high
=FALSE, i.e. there is NO high temperature in the system
2=initialization correct
=TRUE, i.e. system initialization is NOT correct
4=remote shutoff command active
=FALSE, the command is NOT active
8=auxiliary input on system card
active
= TRUE, the input is active.
KEY MENU 8
"ARROW UP": NORMAL
NORMAL OPERATION
M100,
OUT=100%VA
BATT.=100%Ah
5=ON
Access to the menu NORMAL is with key 8 from menu 1 HELP and from all the other menus in which no other
function is provided.
In addition, the system returns AUTOMATICALLY to the menu NORMAL,
i.e. the basic
menu,
always after two minutes after last pressing a key.