1.4 Specification

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

When

 

input

 

voltage

 

is

 

187V

 

with

 

rated

 

full

 

load,

 

and

 

charger

 

works

 

fully,

 

UPS

 

can

 

have

 

the

 

maximum

 

current.

 

 

Load

  

of

  

the

 

high

 

altitude=rated

  

power

 

×Rating

 

factor(correspond

  

to

 

altitude) 
 
 
 
 
 
 
 
 
 
 

Altitude

 

(m)

 

1000

 

1500

 

2000

 

2500

 

3000

 

3500

 

4000

 

4500

 

5000

 

Rating

 

Factor

 

100%

 

95%

 

91%

 

86%

 

82%

 

78%

 

74%

 

70%

 

67%

 

 

Содержание JP5530 10K/RM10K

Страница 1: ...USER S MANUAL JP5530 6 20KVA...

Страница 2: ...her instead of liquid fire extinguisher in case of fire Notes for Electricity 1 Please confirm whether the UPS already connect to the ground check the cable and battery before start the UPS 2 When mov...

Страница 3: ...it is very dangerous 6 Short circuit of the two poles on a battery should not happen otherwise there will be fire or electric shock Maintenance 1 Life of UPS will be subject to the environment don t u...

Страница 4: ...Connection to the computer 11 2 6 Parallel optional 12 2 7 Installation for SNMP optional 15 2 8 EPO 16 2 9 Maintenance switch optional 17 2 10 Dust screen optional 18 2 11 Isolated transformer option...

Страница 5: ...oad disappear UPS will transfer to the inverter automatically This user manual can be applied for the following models JP5530 6K RM6K standard backup type with internal batteries JP5530 6KL RM6KL long...

Страница 6: ...d Meaning Attention Danger AC power DC power Protective Earth Conductor Protective Bonding Conductor Cycling Not Placed With Other Things Overload Battery On Off Button JP5530 6K 10K 15K 20K JP5530 6K...

Страница 7: ...3 JP5530 RM6K 10K JP5530 RM15K 20K 1 3 Rear Panel JP5530 6K JP5530 10K...

Страница 8: ...4 JP5530 6KL JP5530 10KL JP5530 15 20K...

Страница 9: ...maintenance switch maintenance switch is optional terminal board bracket for cable EPO optional Please Note 1 If UPS is with parallel card and maintenance switch please remove board and you will see...

Страница 10: ...th rated full load and charger works fully UPS can have the maximum current Load of the high altitude rated power Rating factor correspond to altitude Altitude m 1000 1500 2000 2500 3000 3500 4000 450...

Страница 11: ...o the ground 2 Installation 2 1 Check when open the package 1 Open the package and check whether there is any damage during the transportation 2 If there is any damage or lack of some instruments plea...

Страница 12: ...on Model JP5530 6K RM6K JP5530 6KL RM6KL JP5530 10K RM10K JP5530 10KL RM10K L JP5530 15K RM15K JP5530 20K RM20K Input G 10AWG 6mm 2 10AWG 6mm 2 8AWG 10mm 2 8AWG 10mm 2 6AWG 25mm 2 6AWG 25mm 2 N 10AWG...

Страница 13: ...input output cable connect the terminal fasten Terminal for UPS JP5530 6KL JP5530 6K JP5530 10KL JP5530 10K 7 Fix the cover plate with screws again 8 Connect wires and get mains then turn on the Inpu...

Страница 14: ...battery cabinet and UPS refer to table 2 2 An air DC switch must be connected between UPS and Battery groups the voltage and current of this switch cannot be less than parameters on batteries of each...

Страница 15: ...er socket Socket o f computer RS232 or USB will connect the UPS to the monitor 1 Connect the RS232 or USB to the socket of computer 2 Connect the RS232 or USB to the socket of UPS The feet bitmap of c...

Страница 16: ...lel cards and cables in this range 2 Installation for parallel This function is optional the user can buy parallel card and cable for installation and maximum three UPS for parallel each UPS must use...

Страница 17: ...rence of each wire which connects block and loads must be less than 10 if the distance between loads and every paralleled UPS is more than 20 meters 3 The input and output terminals of each paralleled...

Страница 18: ...nd transfer to inverter Start UPS when battery supply power press button of each UPS for a short time then press any one of the UPS for a longer time the other UPS will start and work at the battery m...

Страница 19: ...optional Install AS400 card to the socket the position as below meaning PIN1 Break over UPS fault PIN2 Break over alarm PIN3 Ground PIN4 Shut off UPS remote control PIN5 Public terminal non break over...

Страница 20: ...16 2 8 EPO EPO Emergent Power Off is on the real panel of UPS is green terminal 1 2 Close UPS shut off immediately 3 4 Doesn t work...

Страница 21: ...3 4 Open UPS shut off immediately 2 9 Maintenance Switch To realise online service of UPS following picture no matter mains battery or bypass mode internal sections of UPS have power maintenance switc...

Страница 22: ...this wan UPS can be saved without dust Installation of the dust screen as below 1 Remove front panel 2 Install dust screen 3 Install front panel 2 11 Isolated transformer box optional Isolated transf...

Страница 23: ...the mains mode means load at the battery mode means battery capacity 7 bypass orange 8 mains green 9 inverter green 10 battery orange 11 load capacity From right to left 6 2 the more LED flash less l...

Страница 24: ...speaker mute press more than 2 seconds at bypass or battery mode battery check press more than 2 seconds at mains mode 14 start shut off UPS LCD panel 1 5 LED 1 mains green 2 bypass orange 3 battery o...

Страница 25: ...to left battery capacity increase 6 start UPS Start UPS or increase when set the parameter 7 function button Adjust the parameter adjust BUS voltage inverter output voltage and change screen to the n...

Страница 26: ...use UPS at the first time LED status flash not flash Start UPS when the mains supply Press button more than 1 second UPS will start and check itself at this time LED for load battery capacity will fl...

Страница 27: ...t After starting UPS led for battery will flash led for mains will shut off load of the UPS will be supplied by the battery battery mode At the battery mode buzzer will alarm every 4 seconds if need l...

Страница 28: ...er alarm every 2 mints press loudspeaker mute more than 2 seconds if not need output disconnect mains 4 3 Start UPS on LCD Panel Start UPS with mains Press the button for more than 1 second UPS will s...

Страница 29: ...th DC Press the button more than 1 second UPS will start After starting battery light flashes mains light will be off load will be supplied power by the battery Battery Inverter Mode At the battery mo...

Страница 30: ...ut 5 Maintenance of the battery UPS will charge the battery all the time If UPS is not used for a long time charge the battery every 4 6 months If the temperature around is high charge or discharge th...

Страница 31: ...or the frequency of the mains is out of the range of UPS UPS is at the mode of battery save the data shut off the software make sure input voltage and frequency is within the range 1 2 flash the buzz...

Страница 32: ...95 load No 5 96 105 load No 6 Batter y mode 0 20 battery Alarm every 1 second 7 21 40 battery Alarm every 4 seconds 8 41 60 battery Alarm every 4 second 9 61 80 battery Alarm every 4 second 10 81 100...

Страница 33: ...m continuously 18 High temperature Alarm continuously 19 Inverter abnormal Alarm continuously 20 Output short circuit Alarm continuously 21 BUS voltage abnormal Alarm continuously 22 Charger or batter...

Страница 34: ...ery E7 Charger fault E8 Eeprom fault E9 EPO switch wrong F1 CAN cable fault F2 Short circuit of inverter voltage F3 Overload F4 High temperature F5 BUS voltage too high or too low F6 Too high or too l...

Страница 35: ...r board and replace it 6 F 01 Reason CAN cable fault Check Check the control board 7 F 02 Reason Short circuit of inverter voltage Check Check whether output short circuit 8 F 03 Reason output Overloa...