JAGA N.V. | STRADA HYBRID - ACO | MANUEL | 2021.06.03 | V.01
4⁰C
1⁰C
1⁰C
2⁰C
Standby mode
Only in combination with a suitable heat
pump and control valve for heating and
cooling
The device automatically enters cooling mode when the water temperature is 2°C/4°F below the
room temperature. If the differential between room and water temperature is less than 1
°
C/2°F, the
device will automatically switch to standby. The unit starts at the last selected speed(1, 2 or 3), if the
water temperature < 24 ̊C.
Make sure that the thermostat head is set to ‘K’ when cooling.
The unit is in standby. The unit automatically starts a new cycle if the preset temperature is rea-
ched.
The device automatically enters heating mode when the water temperature is 4
°
C/7°F above the
room temperature. If the differential between room and water temperature is less than 1
°
C/2°F higher
than the room temperature, the device will automatically switch to standby. The unit starts at the last
selected speed(1, 2 or 3), if the water temperature > 28 ̊C.
De breeze mode is switched on and off manually. The auto-change-over is disabled as long as the
breeze mode is active. The unit starts at the last selected speed (1, 2 of 3), regardless of the water
temperature.
3.1. OPERATION
Blue LEDs are flashing: the water temperature for cooling is too high
Red LEDs are flashing: the water temperature for heating is too low
MODE
MODE
MODE
MODE
Check the water temperature sensor
Check the room temperature sensor
Control panel error codes
LED flashes rapidly in the color of the set mode .