24
JAGA N.V. | CLIMA CANAL - JDPC | MANUEL | 11.02.2021 | V.01
3”
Off
Off
Manually changing the fan speed : short press
Red LEDs
are flashing: the water temperature for heating is too low (< 28 ̊C).
Blue LEDs
are flashing: the water temperature for cooling is too high (> 18 ̊C).
Control :
Press and hold to switch modes (± 3 sec ).
2. 0-10V WITH WATER TEMPERATURE MONITORING
24 V +
GND
1
0-10 V
[7]
2.1. WITHOUT CONTROL PANEL -
Configuration code : DPC.CC71 / DPC.CC72
The device is controlled via BMS.
The unit starts if the water temperature is > 28°C/82 ̊F and the control signal is 0-10V.
Only with configuration code DPC.CC72. The unit starts if the water temperature is < 18 ̊C/64 ̊F
and the control signal is 0-10V.
Fan speed in function of the incoming control signal.
DPC.CC25