45
EN
JAGA NV | BRIZA 12 - STAND ALONE / BUILT-IN | MANUAL | 2021.02.11 | V.10
4.3. BUILT-IN MODEL WITH AIR OUTLET CORNER PIECE
min. 11
1
min. 11
max. 230
min. 16
1
min. 11
max. 260
5. OPERATING LIMITS
If the unit is filled with cooling water, the condensation that is formed on the coil will be discharged
via the condensate drain connection. If the cooling water temperature is very low or the air humidity
is very high, condensation might form on other components than the coil. This condensation is not
collected in the condensate drain, but may drip under the unit. To prevent this, a minimum permitted
water temperature must be taken into account in function of the relative humidity and the ambient air
temperature.
Permitted minimum water temperature (°C)
AMBIENT TEMPERATURE / DRY-BULB TEMPERATURE (°C)
21 °C
23 °C
25 °C
27 °C
29 °C
31 °C
RH (%)
40 %
3
°C
3
°C
3
°C
3
°C
3
°C
4
°C
50 %
3
°C
3
°C
3
°C
3
°C
4
°C
6
°C
60 %
3
°C
3
°C
4
°C
4
°C
6
°C
8
°C
70 %
3
°C
4
°C
5
°C
6
°C
8
°C
10
°C
80 %
4
°C
5
°C
6
°C
8
°C
10
°C
/
90 %
5
°C
6
°C
8
°C
10
°C
/
/
100 %
6
°C
8
°C
10
°C
/
/
/
Permitted minimum water temperature