Remove plug at hydraulic connection.
Connect the device to the hydraulic system by using the specified inlet/ outlet connections. Make sure that the connections are air tight,
use a sealant for this. The coil is equipped with a de-aerater.
Wall mounted model
ceiling-mounted-model
07
Install the condensate drain. The device must be hung with a downward slant towards the condensate drain, to ensure that the conden-
sation water is drained quickly.
If the condensation drain pan is not used, the drain pipe must be connected directly to the condensation trap. In this case, the
hydraulic pipes and the valves used for cooling water must be insulated against condensation.
ceiling-mounted-model
3 cm/m
3 cm/m
Wall mounted model
08
The condensate drain system must be set up with an adequate p-trap in order to prevent the infiltration of odours. Always install a plug
for cleaning in the lower part of the p-trap in order to allow quick disassembly.Pour water into the condensate collection pan and check if
the liquid is drained properly. Otherwise, check the inclination and look for possible blockages. Position the drain pipes without mechani-
cal stress on the drain connection of the unit.
09
6.1. HYDRAULIC CONNECTION
Hold the hydraulic connection during the installation!