C. AUTO-CHANGE-OVER
4⁰C
1⁰C
1⁰C
2⁰C
Standby mode
Only in combination with a suitable heat
pump and control valve for heating and
cooling !
Configuration code : DPC.BRC3 / DPC.BRC4 / DPC.BRC6
ONLY DPC.BRC4 /
DPC.BRC6
The device automatically enters cooling mode when the water temperature is 4°C/7°F below the
room temperature. If the differential between room and water temperature is less than 2°C/4°F, the
device will automatically switch to standby.
The device automatically enters heating mode when the water temperature is 4°C/7°F above the
room temperature. If the differential between room and water temperature is less than 1°C/2°F
higher than the room temperature, the device will automatically switch to standby.
24 V +
GND
1
2P
4P
MODE
[C]
C.1. FACTORY SETTINGS
C.1.1. Without control panel
- DPC.BRC3
The unit automatically enters the desired operating mode ( or standby) based on the water and room
temperature. (
,
of standby).
Auto-change-over. The unit starts when the water temperature > 28 ̊C.
Auto-change-over. The unit starts when the water temperature < 18 ̊C.
The unit is in standby.
1 Speed . The unit runs at the preset speed.