Jafar 2312 Скачать руководство пользователя страница 6

 

 

 

 
 

OPERATING MANUAL 

11-2020 

6/8 

 
 

 

4.

 

STORAGE & TRANSPORT 

 
The products are packed

 

on EURO pallets (1200x800 mm) or in custom containers, as applicable. Store the valves 

in

 

clean indoor rooms

 

without bacteriological

 

or chemical contaminants and at a room temperature between -20

°

and 70

°

C. Protect the paint coat and rubber parts from

 

prolonged exposure to UV radiation. The filters should be 

protected against mechanical damage.  
Protect  the  rubber  parts  from  compression  by  keeping  the  gate  valve  wedge  closure  halfway  open.  Secure  the 
products against shifting during shipping and handling. The gate valves shall be handled on slings and secured 
from rotating. 
 

5.

 

INSTALLATION  

 
The  flanged  gate  valves  with  soft  seals  intended  for  gas  flow  isolation  in  NG  pieline  systems  and  other  fluid 
systems,  can  be  installed  in  underground  pipelines  or  overground  pipeline  installations,  both  horizontal  and 
vertical, with any direction of flow of the medium. The Type 2312 gas gate valves are intended for installation 
between  resistance-welded pipeline  ends.  The  Type  2314 gas  gate  valves  are  intended  for  installation  between 
fusion-welded pipeline ends. Note that the completed installation must not expose the valve to bending or tensile 
stress from loading with the unsupported pipeline sections, and the valves must be installed aligned with the piping. 
Consider  proper  compensation  of  the  pipeline  dimensional  changes  from  temperature  and  pressure  in  the 
installation.  The  gate  valve  is  ready  for  installation  as  assembled  and  adjusted  by  the  manufacturer.  Any 
dismantling of the gate valve components may result in loss of seal. 
Before attempting to install the valve, check the technical and commercial documents delivered with the product 
to  verify  that  your  media  and  pipeline  operating  parameters  comply  with  the  manufacturer's  declaration.  Any 
change in the operating conditions must be consulted with the manufacturer beforehand. 
Before attempting to assemble the valve, remove the main bore plugs, check the inner surfaces of the valve and 
thoroughly flush with water, if necessary. Install the gate valve on a base or a support adequate to the size and 
weight of the valve, to prevent strain of the piping with the valve. Use suitable piping flanges, gaskets and bolts 
for the valve flange ends. The valve and piping flange holes must be aligned. Tighten the connection flange bolts 
crosswise  to  ensure  a  proper  seal  pressure.  The  gate  valve  location  must  prevent  exposure  to  freezing  of  the 
medium flowing through the gate valve. Equip the gate valve with a suitable control, e.g. a spindle handwheel with 
a flexible or rigid housing, an electric drive unit and a pedestal. When installing a housing, it is necessary to equip 
the unit with a street box founded on a base slab. When using a spindle extension, make sure that the weight of the 
extension is not transferred to the gate valve spindle. To prevent the load transfer, use holding pieces, mounted to 
the  chamber/vault  walls.  Spindle  extensions  over  3000  mm  long  shall  be  attached  via  Cardan  joints.  Having 
completed  the  installation,  perform  a  pressure  test  at  a  maximum  test  pressure  equal  to  1.5  times  the  nominal 
pressure. 
 
Caution! If the product has mechanical damage, do not install it in the pipeline. 

6.

 

OPERATION AND MAINTENANCE 

 

 

The gate valve shall be operated in accordance with all relevant requirements for stop valves, i.e. kept either in the 
fully open or fully closed position. Leaving the gate valve partially opened (or closed) may result in seal failure.  
The gate valve can be controlled with: 

 

a handwheel sized according to the Product Specification Sheet and mounted on the gate valve spindle or a 
pedestal; 

 

a T-socket wrench, if the spindle neck is in a housing; 

 

an electric or pneumatic drive unit; 

 

other driving gear, e.g. a handwheel with a chain. 

Valve control requires a specific driving torque (see table in Section 2) and a specific number of spindle turns. Do 
not exceed the maximum driving torque. 
 
To  ensure  full  operational  efficiency,  carry  out  a  technical  inspection  and  maintenance  at  least  once  a  year  as 
follows: 

 

Operate the gate valve from the fully open position to the fully closed position, or vice versa, as the case may 
be. 

 

Follow the driving torque limits specified in the table in Section 2. 

Содержание 2312

Страница 1: ...OPERATING MANUAL 11 2020 1 8 OPERATING MANUAL Flanged gate valves with soft seals P N 2312 2314 ...

Страница 2: ...G MANUAL 11 2020 2 8 TABLE OF CONTENTS 1 INTENDED USE 3 2 TECHNICAL DESCRIPTION 3 3 PRODUCT IDENTIFICATION MARKING 4 4 STORAGE TRANSPORT 6 5 INSTALLATION 6 6 OPERATION AND MAINTENANCE 6 7 SAFETY 8 8 WARRANTY 8 ...

Страница 3: ...n of the gate valve has the clockwise closing sense of rotation The closing sense of rotation can be opposite on special order Installation length in accordance with plant documentation Nominal pressure ratings 1 0MPa 1 6MPa The flanged gate valves with soft seals intended for gas flow isolation in NG pieline systems and other fluid systems feature a smooth walled bore a non ring spindle and an o ...

Страница 4: ...king of metallic valves EN 1074 1 Valves for water supply Fitness for purpose requirements and appropriate verification tests Part 1 General requirements The gate valve bodies feature markings on the front and back walls of the body chamber The marking contains the following data manufacturer s trademark heat no nominal diameter nominal pressure body material type ...

Страница 5: ...the piping PN 5 CE marking Maximum permitted pressure PS 6 Maximum minimum permissible temperature TS 7 Barcode 8 Production serial no in the calendar year 9 Seal material 10 Year of manufacture of the product 11 Diameter bore and nominal size DN 12 Reference standard the product is compliant with 13 Product name The gate valves with GSK RAL certified corrosion protection feature the corresponding...

Страница 6: ...nd thoroughly flush with water if necessary Install the gate valve on a base or a support adequate to the size and weight of the valve to prevent strain of the piping with the valve Use suitable piping flanges gaskets and bolts for the valve flange ends The valve and piping flange holes must be aligned Tighten the connection flange bolts crosswise to ensure a proper seal pressure The gate valve lo...

Страница 7: ...her movement this will seal the spindle under the flange 6 This operation allows you to replace the o rings in the plug 3 or the whole plug assembly on the pipeline in operation 8 Clean the gate valve cover from dirt sediments and grime Disassemble the following in the succession shown below the wiper gasket 1 the circlip 2 Release and remove the sealing plug 3 with the service wrench tool availab...

Страница 8: ...rating Manual Follow the general health and safety rules Keep this Operating Manual throughout the service life of the product to ensure a safe operation of the latter 8 WARRANTY The product assembled installed and operated in compliance with this Operating Manual and the Product Specification Sheet is covered by a commercial warranty from the manufacturer The warranty terms conditions and period ...