background image

4

installation

CLEARANCES FROM

COMBUSTIBLE SURFACES:

The Jade Gas Cooktop must be installed in accor-
dance with the minimum clearances as illustrated.
In order to reduce the hazards in reaching over the
appliance, avoid placing cabinets directly above the
cooktop. When installed, the maximum depth of the
overhead cabinets is 13 inches. Note that the
minimum vertical distance between the cooktop
surface and the combustible cabinets above the
cooktop is 50”. If a ventilating hood is used, we
recommend a minimum 30” distance from the
bottom of the hood to the cooktop surface.

Because of the high burner input rate of the Jade

Gas Cooktop, A PROFESSIONAL VENTILAT-
ING HOOD MUST BE INSTALLED ABOVE
THE APPLIANCE IF THE SPACE “W” IS LESS
THAN 48 INCHES FOR A RJCT36 AND
60 INCHES FOR A RJCT48. Please refer to the
chart for the recommended ventilating hood sizes.

For island installation, the minimum clearances are
12” from rear wall, 6” from side cabinets (18”
above cooking surface).

·

The hood width must be at least the same width
as the cooktop. The hood depth must be 19”
minimum.

·

The hood must not contain combustible
materials.

·

Due to the high volume ventilation air, a source
of outside replacement air is recommended. This
is particularly important for tightly sealed and
insulated homes.

·

A qualified heating and ventilating contractor
should be consulted when installing the
ventilating hood and associated duct work.

·

Any opening in the wall behind the appliance and
in the cabinet top under the appliance must be
sealed.

Recommended Size

Ventilating Hood

Minimum

Vent Hood Width

30”
36”
48”

Model

RJCT30
RJCT36
RJCT48

Minimum

Vent Hood Size

600 CFM
900 CFM

1200 CFM

All dimensions in inches.

All dimensions in inches.

Содержание RJCT30

Страница 1: ...CAN CGA B149 2 Propane Gas Installa tion Code This appliance must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFA 7...

Страница 2: ...instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier UNPACKING AND INSPEC...

Страница 3: ...p for all models MODEL DIM A RJCT30 30 RJCT36 36 RJCT48 48 Safety Instructions RJCT3080A RJCT3680A RJCT3683A RJCT3681A RJCT4883A RJCT4881A OR ISLAND TYPE INSTALLATION FOR USE ONLY IN PENINSULA ISLAND...

Страница 4: ...RJCT36 AND 60 INCHES FOR A RJCT48 Please refer to the chart for the recommended ventilating hood sizes For island installation the minimum clearances are 12 from rear wall 6 from side cabinets 18 abov...

Страница 5: ...VERITICAL OR HORIZONTAL REGULATOR CONNECTION 3 4 NPT PIPE CONVERTIBLE BUILT IN A 120V 1 PH 60HZ 4AMPS 5 FT ELECTRICAL CORD SIDE TRIM 29 5 8 35 5 8 46 5 8 36 DSCT 36 DSCT 48 TOP COUNTER 48 DSCT 30 MODE...

Страница 6: ...pliance and its individual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1 2 psig 3 5kPa The appliance...

Страница 7: ...hould be plugged directly into a properly grounded three prong receptacle Do not cut or remove the grounding prong from this plug This appliance must be electrically grounded in accordance with local...

Страница 8: ...8 RJCT3080A RJCT3680A RJCT3683A RJCT3681A RJCT4881A RJCT4883A...

Страница 9: ...f heat at the HI setting DO NOT OPERATE THE BURNERS WITHOUT COOKWARE ON THE GRATES THE PORCELAIN ON THE GRATES MAY CHIP IF BURNERS OPERATE FOR AN EXTENDED PERIOD OF TIME WITHOUT COOKWARE ON GRATES The...

Отзывы: