ELECTRICAL POWER
CONNECTIONS
Electrical and grounding conductors must comply with the applicable portions of the
National Electric Code ANSI/NFPA 70 (latest edition) and/or other electrical codes.
The data plate is located at the left front side of the dishmachine. Refer to the data plate
for machine operating requirements, machine voltage, total amperage & serial number.
Remove the back panel to install the incoming power lines. This will require removing
the screw at the bottom of the back panel with a Phillips head screw driver. Remove
the back panel and set aside. Install 3/4” conduit into the pre-punched holes in the
back of the control box. Route power wires and connect to power block and grounding
lug. Install the service wires (L1and L2) to the appropriate terminals as they are
marked on the terminal block. Install the grounding wire into the lug provided. It is
recommended that “DE-OX” or another similar anti-oxidation agent be used on all
power connections.
Ensure that the power button is in the off position and apply power to dishmachine.
Check the incoming power at the terminal block and ensure it corresponds with the
voltage listed on the data plate. If not, contact a qualified service agency (listed at
the end of this manual) to examine the problem. Do not run dishmachine if voltage
is too high or too low. Shut off the service breaker and advise all proper personnel
of the location of the breaker and any problems. Replace the control box cover and
tighten down the screws.
This is a commercial dishmachine and reaches temperatures that can exceed those
generated by a residential machine. Therefore, any surrounding countertops, cabinets,
flooring material & subfloor material must be designed and/or selected with these
higher temperatures in mind. Note: Any damage to surrounding area that is caused
by heat and/or moisture to materials that are not recommended for higher temperatures
will not be covered under warranty or by Jackson WWS, INC.
The temperature setpoints on this Avenger unit have been set at the factory. They
should only be adjusted by an authorized service agent.
DISCONNECT ELECTRICAL
POWER SUPPLIES & TAG
OUT IN ACCORDANCE
WITH APPROPRIATE
PROCEDURES & CODES
AT THE DISCONNECT
SWITCH TO INDICATE
THE CIRCUIT IS BEING
SERVICED.
TEMPERATURE
SETPOINTS
SURROUNDING
AREA
VOLTAGE CHECK
Содержание AVENGER HT-E
Страница 2: ......
Страница 35: ...29 CONTROL PANEL PARTS 1 8 3 2 4 5 6 7 ...
Страница 41: ...35 115V CONTROL BOX PARTS ITE 2 3 4 5 6 7 8 9 13 14 15 4 4 2 5 6 8 9 7 3 1 1 ...
Страница 46: ...40 WASH DRAIN MOTOR ASSEMBLY PARTS 10 11 12 13 1 2 3 4 5 9 8 6 7 ...
Страница 54: ...48 RINSE TANK ASSEMBLY PARTS 8 7 6 5 2 3 4 1 ...
Страница 58: ...52 SCHEMATICS 115 VOLT ELECTRICAL DIAGRAM ...
Страница 59: ...53 SCHEMATICS 208 230 VOLT ELECTRICAL DIAGRAM ...
Страница 60: ...54 SCHEMATICS 480 VOLT ELECTRICAL DIAGRAM ...