Zone Control Made Simple™
5418 Elmwood Avenue, Indianapolis, IN 46203-6025
Toll Free: 888.652.9663 Fax: 317.227.1034
www.jacksonsystems.com
Specifications:
Panel Dimensions:
Mounting:
Operating Temperature Rating:
Operating Humidity:
Wiring:
Time Delays:
Thermostats:
Height:
8.0 Inches
Width:
6.0 Inches
Depth:
1.375 Inches
Snap Track with 2 back plate screws
-40° F to 150° F
5% to 90% RH non-condensing
18-gauge wire for all equipment
and system connections
3 minutes minimum off between
cooling calls
3 minutes minimum off on low limit
20 minute time share
Single-stage heat / cool thermostats
Programmable or non-programmable
Auto or manual changeover
Z NE
N
E
E
R
G
E
H
T
Zone Control Made Simple
TM
TM
Dampers:
High / Low Limit
HVAC Equipment:
Panel Power:
D
Powered Closed / Spring Open
D
(2 wire)
DAS Discharge Air Sensor
DAS (2 wire)
R
24Vac (Hot)
W1
First Stage Heat
W2
Second Stage Heat
Y1
First Stage Cool
Y2
Second Stage Cool
G
Fan
X
24Vac (Common)
H
24Vac (Hot)
Typical System Layout
ZONE DAMPER 2
MIGHT SERVE
BEDROOM AREA
ZONE DAMPER 1
MIGHT SERVE
LIVING AREA
ZONE 1
STAT
ZONE 2
STAT
Z-200-HC-MS
PANEL
24 VOLT 40VA
TRANSFORMER
FURNACE
HIGH/LOW
LIMIT
SENSOR
Terminal Designations:
Thermostats:
C
24Vac (Common)
R
24Vac (Hot)
W1
First Stage Heat
W2 Second Stage Heat
Y1
First Stage Cool
Y2
Second Stage Cool
G
Fan
Z-200-HC-MS Installation and Operation Instructions
2 Heat / 2 Cool - Auto Changeover - First Call Priority - Time Share
06-1035-072011