Sequence Of  Operation 

 

Comfort System™ is a residential / light commer-
cial zone control system that allows a single   
HVAC unit to have up to three separate zones 
(nine if three panels are connected together).  Each 
zone is controlled by its own space thermostat and 
motorized zone damper.  If any of the zone      
thermostats call for heating or cooling, the zones 
not calling will have their dampers powered 
closed, and the zone(s) calling will have its (their) 
damper(s) remain open.  The heating or cooling 
equipment will also be brought on at the same 
time.  When all zone thermostats are satisfied, the 
heating or cooling equipment turns off and all zone 
dampers return to the open position to allow for 
continuous air circulation.  This is a manual 
changeover zone control panel. 

 

Thermostats 

 

The Z-300-HP works with standard,  heat pump 
thermostats.  

All thermostats must be set in the 

same mode.

  Thermostats must 

not

 be set in the 

auto changeover mode. 

Typical System 

Verify that all wires have been connected to the 
proper terminals and are secure. 

 

Verify that the jumper across the “LL” and “HL” 
terminals were removed before connecting the 
high and low limit stats. 

 

The low limit (FS-38) should be connected to the 
“LL” terminals on the zone control panel.  The 
high limit (HL-170-HP) should be connected to the 
“HL” terminals on the zone control panel. 

 

Zone dampers are powered closed and spring     
return open.  There will be no power at the panel 
damper terminals marked “D” when the damper is 
in the open position. 

When a green zone LED is on, that zone is calling 
for heating or cooling. 

 

To check the system for proper operation, pull the 
disconnect for the condensing unit to prevent short 
cycling.  Next, place all the zone thermostat mode 
switches  in  heat  mode  and  turn  down  all           
thermostat set points.  Go to each zone thermostat, 
one at a time, and call for heat to verify that the 
proper zone dampers are open (and the rest are 
closed).  Turn the zone thermostat back down    
before checking the next zone. 

System Checkout 

Zone #1 

Stat 

Zone #2 

Stat 

24 Volt 40VA 

Transformer 

Zone Control 

Panel 

Zone #1 Damper 

Might Serve 

Living Area 

Zone #2 Damper 

Might Serve  

Bedroom Area 