background image

Prelimenary Manual (subject to change) - JA-80IR wireless optical barrier  2 /2 

jemné 

se

ř

ízení

 

Fig. 5 Setting up the optical part 

 

When the setting is complete, it is followed by another step – adjustment 
of the receiver unit: 
 

P

ř

ipojte voltmetr do svorek a 

zvolte rozsah 0 - 10V.

Sledujte LED vpravo

 

 

A permanently lit LED on the right indicates that the beam has been 
interrupted (or wrongly adjusted). The better the beam reception, the 
longer the breaks between the LED flashes. When the LED stops 
flashing, continue looking for the ideal position indicated by the highest 
voltage measured on the voltmeter. 

 

Setting up the electronic part of the barrier 

Both units are equipped with setting switches. The switch located on the side 
of the units (on the optical part) allows barrier beam modulation frequency 
adjustment from 1 to 4. This setting is useful only for a combination of 
multiple JA-80IR barriers where a problem with interference might appear. 
For more information see the original user manual or contact the 
JABLOTRON ALARMS technical support service. 

 

There is a DIP switch with five switches. The first two positions are used to 
set the reaction time to an interruption of the beam. The shorter the time, the 
more precise the interruption detection, but also the greater the susceptibility 
to false alarms during worsened optical conditions (snow, fog, ...)

 

rychlý b

ě

h

(50 ms)

pomalý b

ě

h

(100 ms)

ch

ů

ze

(250 ms)

pomalý pohyb

(500 ms)

 

Fig. 6 Reaction time setting 

 
It is possible to set a 2-minute sleep time after an alarm (beam 
interruption) in order to save batteries. This setting is done by switching 
switch no. 3 (receiver unit), or no. 1 (transmitter unit), as the case may 
be, to the ON position. Switches 4 and 5 (receiver unit), or better 2 and 
3 (transmitter unit) are set as a default and you should leave them in the 
ON position for the correct functioning of the device. 
 

Operation testing  

 
The LEDs on the barrier have the following indication functions 

 

p

ř

íjíma

č

(receiver) vysíla

č

(transmitter) 

slabá baterie 

slabá baterie 

indikace narušení

indikace nap

ě

t

 

Fig 7 LEDs on the units 

 
The battery low signal LEDs flash when the batteries in the unit are low. 
Both batteries 

(SAFT LSH20 lithium batteries) 

should always be 

replaced at the same time.

 

The interruption LED flashes during beam blocking. 
The voltage indication LED flashes when the battery in the transmitting 
unit is OK. 
 

p

ř

íjíma

č

(receiver) 

vysíla

č

(transmitter) 

 

Fig. 8 Barrier function test 

 
Perform a barrier test in three places (A B and C). The setting is 
completed only if the barrier reacts successfully in all three positions. 
You should also check the signal transmission to the system control 
panel. Only then is it possible to put back the unit covers and secure 
them. 

 
 

Checking the status of and replacing batteries 

 

The detector checks battery status automatically and if the batteries are 
running low, it informs the system that they need replacing. The detector 
remains fully functional.  The batteries should be changed as soon as 
possible (within 1 week). Use 

SAFT LSH20 batteries exclusively

 and 

always replace both at the same time.  

 

Technical specifications 

 

Power supply 

4x LSH20 type lithium batteries (3.6 V 13 Ah)

 

Average battery lifetime 

approx. 3 years (with 120 s energy saving mode)

 

Operating frequency 

868 MHz

 

Radio range – distance from the control panel 

up to 300 m with direct visibility

 

Optex barrier parameters 
Distance (max.) between the barrier units 

60  m

 

Barrier installation height 

0.7  – 1.0 m

 

Object motion speed 

as set by user

 

Battery saving timer 

120 s

 

Detector cover conformance 

IP55

 

Max. relative humidity of the environment  

95%

 

Weight  

620 g

 

Environment according to EN 50131-1.   

IV

 

Operating temperature range 

-20°C to +60°C

 

Security rating

 Grade 

2

 

 

According to EN 50131-1, EN  50131-2-2, EN 50131-5-3 

 

Can be operated according to 

CTU VO-R/10/06.2009-9

 

 
 

 

Отзывы: