MFJ51212

 

7.4 

Events to be reported  to CMS 

 

There are 31 types of events, which can be reported to each CMS – 
see table 7.4.1. This sequence sets which events should be reported 
to CMSs. 

 

 

05 p uu y 

 

where  

p  

1 = CMS1, 2 = CMS2 

uu

  

events index – see table 7.4.1 

y  

0 = report disabled, 1 = report enabled 

 

 

Default setting:  all reports are disabled 
 

7.4.1 

Table – complete list of events to be reported to CSM 

Events index uu 

Events description 

01 

 Intruder alarm – instant zone 

02 

 Intruder alarm – delayed zone 

03  

Fire 

alarm 

04 

 Panic alarm  

05 

 Wrong access code alarm 

06 

 Alarm after power on  

07 

 Tamper alarm 

08 

 Tamper OK 

09  

Alarm 

end 

10 

 Alarm canceled by a user 

11  

Arming 

12  

Disarming 

13 

 Partial arming (Home) 

14 

 No code arming 

15 

 External communication failure 

16 

 External communication recovery 

17  

Failure 

18 

 Failure recovery 

19 

 AC failure longer than 30 minutes 

20 

 AC failure 

21 

 AC recovery 

22 

 Battery failure 

23 

 Battery recovery 

24 

 Enter programming mode 

25 

 Exit programming mode 

26 

 Remote access 

27 

 Remote access – end 

28 

 RF jamming 

29 

 Internal communication failure 

30 

 Internal communication recovery 

31 

 Periodic test 

7.5 

CMS re-dialing pause setting 

 

If the dialer is activated it attempts to make a connection (alternating 

between the primary and the backup telephone number). If it is not 
possible to make a connection, a pause is initiated. After this pause 
the dialer will attempt again. The pause length can be set in the 
following way: 

 

 

06 p t

          

where 

pause duration

 

x 5 minutes  (1 = 5 minutes, 2 = 10 

min,..., 9 = 45 minutes)

 

p  

1 = CMS1, 2 = CMS2 

 

Default setting: 5 minutes for both CMSs 

 

7.6 

Interval of periodic test 

 

The periodic test for checking the CMS link is set by activating event 

No 31. The following sequence sets the time length from the last 
reported event to the moment when the periodic test report should be 
transferred.   

 

 

07 p hhmm 

where 

p  

1 = CMS1, 2 = CMS2 

hh 

hours 

mm 

minutes 

 

Default setting: The periodic test report is sent 24 hours after the last 
reported event.  

 

7.7 

Disabling CMS communication  

 

If you need to disable all CMS reports temporarily, you can do this, 
while retaining your settings: 

 

0 0 p 0

  

all

 

reports to CMS 

p

 disabled 

 

0 0 p 1

  

all reports to CMS 

p

 enabled  

 

Default setting:

  all CMS reports disabled. 

 

 

7.8 

CMS 2 as a back up for CMS1  

 

CMS 2 can serve as an optional back-up for CMS if data transfer to 
CMS1 fails. When the first event is transferred to the backup 
monitoring station (CMS2) an event “tel. line #1 communication fault“ 
will be reported. 

 

080

    CMS1 and CMS2 are two independent stations 

081

    CMS 2 works as a back up for CMS 1. 

 

When 081 is selected, CMS 2’s settings are used only in the case of 
CMS 1 transfer failure.  

 

Default setting

: two independent CMSs. 

 

7.9  Storing the event “data to CMS sent” into the event memory 

By this sequence it is possible to disable recording of the event that 
indicates that data to a CMS has been sent to the list of event in the 
control panel.  

Programming sequences: 

090

  

The CMS data transfer event is not recorded  

091

  

The CMS data transfer event is recorded  

Default setting

:

 

The CMS data transfer event is recorded

  

 

The modem function 

The GSM communicator can also be used as an external modem for 
accessing the Internet (GPRS format).  It is necessary to have GPRS 
activated in the SIM card and to have a connection cable connected to the 
COM port of the PC. Support for MS Windows operating systems can be 
found on the enclosed CD.  The modem can only be used when all CMS 
reports, SMSs and system calls have been  executed. 
When the modem is used:  

ƒ

  It is possible to use the attached telephone, the internet connection will 

be temporally suspended  

ƒ

  Received SMSs are stored and they will be processed after modem 

disconnection 

ƒ

  The modem will be disconnected if an alarm or an arming event occurs

 

 

9 Additional 

information 

 

9.1 

Priorities for event reporting: 

If the dialer is activated to send an event report it will: 

ƒ

 

send information to CMS1 (trying primary and back up 
numbers twice) if programmed 

ƒ

 

send information to CMS2 (trying primary and back up 
numbers) if programmed 

ƒ

 

send SMS reports (1

st

 telephone number, 2

nd

 telephone 

number,…. 8

th

 tel. number)  

ƒ

 

send audible reports (1

st

 telephone number, 2

nd

 telephone 

number,…. 8

th

 tel. number) – each number is only called 

once, whether it is answered or not 

ƒ

 

if the attempt to send a report to a CMS has not been 
successful, the dialer will try to resend it after the re-dialing 
pause (sequence 06px). The dialer will make three attempts 
at sending event reports to a CMS, i.e. it will wait (according 
to the setting 06px) twice for the re-dial pause. Only a new 
event will result in an additional attempt to call the CMS. 

 

If any event is triggered which should be reported to a CMS while the 
alarm system is being remotely accessed by phone, the report will be 
sent after remote access has finished.  

 

If a user cancels an alarm, all reports, which have not been sent yet, 
will be deleted, except for CMS reports.  
 

9.2 

The LED on the dialer PCB 

 

 

LED flashing means the dialer has not entered the GSM network 

 

LED flashing (3x) – the communicator (modem) is controlled by a PC.

 

 

LED being on means– communication with a GSM network 

  connecting to  the GSM network 

  the dialer is calling 

  the dialer is sending an SMS 

 

9.3 

Entering programming mode 

 

 

The dialer will finish the current CMS connection (the attached 
phone will ring shortly to confirm this) 

 

The current audible warning is interrupted immediately 

 

SMSs and audible warnings, which remain unsent before entering 
programming mode, are erased – they will not be sent after exiting 
programming mode 

Содержание JA-60GSM

Страница 1: ...elephone set can be attached to the dialer The PHONE output of the dialer should never be connected to any other telephone network g If you use the AUX output to control an appliance connect its cable to the AUX output terminals normally open dry contact max 100mA 60V see figure 1 S Y M BO L SPA C E CANCEL MENU NAMES CALLS WRITE READ 1 2 3 4 5 6 7 8 9 0 2 S MS C A LL MUT E FLASH REDIAL SPEAKER fig...

Страница 2: ...y an SMS reply If the alarm system is split the instruction will effect the section which belongs to the access code used If arming without a code is enabled on the control panel the AM command can be used without any access code In this case the command performs the same action as the keys F 1 pushed on a keypad 2 5 Disarming by SMS DM xxxx Command DM followed with a valid access code will disarm...

Страница 3: ...JA 60GSM dialer module 3 MFJ51212 2 10 ...

Страница 4: ...e a From an authorized phone dial the JA 60GSM phone number The SP 01 will ring once and then it will answer the call b Potential alarm on the control panel will be terminated c You can talk to the premises d For switching to the listening mode press 5 on your phone For switching back to the talking mode press key 2 Or by pressing button 1 it is possible to toggle between talking and listening e P...

Страница 5: ...ther with each corresponding index number It also shows which events are assigned to which telephone numbers to be reported by SMS You can make your own setting by using 81 uu t y where uu is the event index from 01 to 31 see table 4 1 1 t is a telephone number memory location from 1 to 8 y 0 reporting disabled 1 reporting enabled Note SMS reports consist of 4 text parts installation name event na...

Страница 6: ...ireless detector 15 14 No code arming 416 Wireless detector 16 15 External communication failure 501 User code 1 16 External communication recovery 502 User code 2 17 Failure 503 User code 3 18 Failure recovery 504 User code 4 19 AC failure longer than 30 minutes 505 User code 5 20 AC failure 506 User code 6 21 AC recovery 507 User code 7 22 Battery failure 508 User code 8 23 Battery recovery 509 ...

Страница 7: ...RF jamming 29 Internal communication failure 30 Internal communication recovery 31 Periodic test Example if you enter 820381 and a Fire alarm is triggered event index 03 the dialer will call the 8 th telephone number and it will play audible warning if the call is answered 4 4 Temporarily disabling SMS and audible reports If you need to disable all SMS and audible reports temporarily to all teleph...

Страница 8: ...to the first ring of any incoming call Without requesting the access code it will enable the calling phone s keypad to be used as the keypad of the alarm system F N This mode will be disabled after you dial in or after you exit programming mode 5 9 GSM signal monitoring Enter 971 on the alarm system keypad in programming mode to measure the GSM signal strength The keypad will show a number from 0 ...

Страница 9: ...mming mode in the communicator using ComLink software 5 17 GSM module reset Enter 976 to disconnect and connect the GSM module to the GSM network This function is useful when it is necessary to switch the mobile device off and on e g when the SIM card has been unblocked by the mobile operator It is also possible to send the command via SMS in the form yyyyy GSM where yyyyy is service access code T...

Страница 10: ...ng two independent CMSs 7 9 Storing the event data to CMS sent into the event memory By this sequence it is possible to disable recording of the event that indicates that data to a CMS has been sent to the list of event in the control panel Programming sequences 090 The CMS data transfer event is not recorded 091 The CMS data transfer event is recorded Default setting The CMS data transfer event i...

Страница 11: ... bands E GSM GPRS 900 1800MHz transmitted power 2 W for GSM900 1 W for GSM1800 AUX output dry contact max 100mA 60V comply with EN 50131 1 EN 50136 2 1 2 3 2 4 security grade 2 low to medium risk environmental class II indoor general 10 to 40 C safety EN 60950 EMC EN 301489 1 EN 301489 7 EN 55022 EN 50130 4 radio characteristics ETSI EN 301419 1 EN 301511 Caller line identification presentation CL...

Страница 12: ...st ring without the access code Measuring of GSM signal 971 If entered while in programming it shows GSM signal strength from 0 to 9 Volume adjustment of the connected phone 974x 975x Level adjustment of received and outgoing signal from 1 to 9 5 medium level GSM Module Reset 976 If entered while in programming mode the GSM module will be disconnected from and connected to the GSM network It is al...

Отзывы: