background image

JABLOTRON

ALARMS

a.s.

Pod

Skalkou

4567/33

46601

Jablonec

n.

Nisou

Czech

Republic

www

.jablotron.com

||

|

The JA-110ST Bus combined smoke and heat fire detector

The JA-110ST Bus combined smoke and heat fire detector 

1 / 2 

MLW51605 

The JA-110ST is a component of the JABLOTRON JA-100 system. 

It is used to detect fire hazards in a building interior.  The product is not 
designed to be installed in industrial premises. The JA-110ST consists 
of an optical smoke detector and a heat detector. The optical smoke 
detector is very sensitive to large dust particles which are present in 
dense smoke. It is less sensitive to smaller particles generated by the 
combustion of liquids such as alcohol. That is why the fire detector also 
contains a built-in heat detector which has a slower reaction but is 
much better at detecting fire which generates only a small amount of 
smoke. The detector has a status reaction (reports its activation and 
deactivation). The detector should be installed by a trained technician 
with a valid certificate issued by an authorized distributor.

Detector location 

The smoke detector must be installed so that any smoke easily drifts 

into the detector owing to natural thermal currents (usually on the 
ceiling).  The detector can only be used in enclosed interiors. It is not 
suitable for interiors where smoke can disperse over a large area and 
cool down (e.g. interiors with extremely high ceilings – above 5 m) – the 
smoke would not reach the detector position.

The detector must always be placed in the section leading to the exit 

of the building (escape route), see Figure 1. If the building has a floor 
area greater than 150 m

2

, installation of an additional detector in some 

other suitable place is required, see Fig.2. 

1

2

3

4

5

Fig 1 

1

2

3

4

5

6

Fig 2

1

2

3

6

Fig 3

1. kitchen,  

2. living room,  

3. – 6. 
bedrooms  

y

 /

basic  
coverage

{

recommended 
coverage 

It is recommended to place additional detectors in rooms where 

people sleep.  

Installation on level ceilings 

Place the detector in the centre of the room if possible. 

The detector 

must not be recessed into the ceiling

 due to the possible existence 

of a cool air layer on the ceiling.

 Never place the detector in the 

corner of the room 

(always keep at least a 0.5 m distance from the 

corner) see Fig 4. There is an insufficient circulation of air in corners. 

Installation on sloping ceilings 

If the ceiling is not suitable for mounting on a level surface (e.g. a 

room under a roof ridge), the detector can be installed as in Fig. 5. 

0.5m

TOP

Fig 4 

0,9 m

Fig 5 

centre of the room, best location 

acceptable location 

Walls, partitions, barriers and lattice ceilings 

The JA-110ST detector must not be installed closer than 0.5 m 

from any wall or partition. 

A narrow space with a width of less than 

1.2m requires the detectors to be placed at a distance of at least one 
third of its width away. In a case when a room is separated into 
sections with furniture, racks or semi partition walls which do not reach 
the ceiling, the space is considered to be fully separated if the gap 
between the top of these and the ceiling does not exceed 0.3 m.   
A free space of at least 0.5m is required under and around the detector. 
Any irregularities of the ceiling (e.g. girders) exceeding 5 % of the 
ceiling height should be considered a wall and the above-mentioned 
limitations should apply. 

Ventilation and air circulation 

The detectors must not be installed directly by ventilation or air 

conditioning vents, etc.

 In the case of air being supplied through a 

perforated ceiling, each detector must be placed so that no perforation 
hole occurs within 0.6 m of the detector.

Avoid installing the detector in the following locations:

  places with poor air circulation (niches, corners, apexes of 

 

A-shaped roofs, etc.) 

 

places exposed to dust, cigarette smoke or steam 

  places with over-intense air circulation (close to ventilators, heat 

sources, air conditioning outlets, etc.) 

  in kitchens and other cooking places (because steam, smoke or 

oily fumes can cause false alarms or reduce detector sensitivity). 

  beside fluorescent lights or energy-saving light bulbs (electrical 

interference can cause a false alarm) 

 

in areas with lots of small insects 

Warning: Most false alarms are caused by improper 

detector location.

See CEN/TS 54-14 standards for detailed installation guidelines.

Installation 

When installing the detector, abide by the procedures 
recommended in the previous paragraphs. 

1

2

3

BUS

1400- 0 0- 0000- 000 1

5

4

6

Fig 6: 1– detector cover opening (removal); 2 – detector cover closing 

(insertion); 3 – optical signalling; 4 – arrow showing where to insert the 

detector; 5 – bus connection terminals; 6 – production code; 

1. 

open the detector cover, by turning it anti-clockwise 

2.  Insert the bus cable 

and attach the plastic base

 to the selected 

place using screws. 

3.  Connect the bus cable. 

Отзывы: