The JA-110ST Bus combined smoke and heat fire detector

The JA-110ST Bus combined smoke and heat fire detector 

2 / 2 

MLW51605 

When connecting the module to  
the bus, always switch the power off. 

4.  Proceed according to the control panel installation manual. Basic 

procedure: 
a.  When the device is powered, the yellow LED starts flashing 

repeatedly to indicate that the module has not been enrolled 
into the system. 

b. 

Go to the 

F-Link

 program, select the required position in the 

Devices

 window and launch the enrollment mode by clicking 

on the 

Enroll

 option. 

c.  Insert the detector into the plastic base. It can only be inserted 

in the position marked with arrows on both plastic parts. Close 
the detector by turning it clockwise. The tamper contact inside 
the detector is thus triggered and the detector is enrolled. The 
yellow LED indicator goes off. 

Detector settings

Go to the 

Devices 

window in the F-Link program. When you are at 

the detector position, use the 

Internal settings

 option to open a dialog 

window where you can set: 

LED indication enabled:

 allows disabling the red LED used to 

indicate activation.

Means of detecting

 – smoke only, heat only, smoke and heat at the 

same time, smoke or heat. 

Detector testing and maintenance 

The functioning of the detector can be tested with a special spray 

designed for smoke detector testing to simulate fire. The valid EN 
standards recommend you to perform 

detector testing once in 30 

days.

 The detector must be regularly cleaned of dust, cobwebs, etc.

Warning: never test the detector with fire. 

Fault indication 

The detector checks its functioning automatically. When it discovers a 

fault, it indicates it with the yellow LED indicator. In such a case, 
disconnect the power supply for 1 minute and then reconnect it. If the 
LED indicator starts lid permanently again after 1 minute, send the 
detector to a service centre.

Technical specifications 

Power 

from control panel digital bus 12 V (9…15 V)

Current consumption in standby mode 

5 mA

Current consumption for cable selection 

 10 mA

Dimensions 

diameter 126 mm, height 50 mm

Smoke detection 

optical light scattering

Smoke detector sensitivity 

 m = 0.11 - 0.13 dB/m pursuant to EN 54-7

Heat detection 

class A2 according to EN 54-5

Alarm temperature 

60°C  to 70°C   

Operating temperature range 

-10°C to +80°C  

Complies with   

EN 54-5, EN 54-7 

 

EN 50130-4, EN 55022  

JABLOTRON ALARMS a.s. hereby declares that the JA-110ST module is in 
compliance with the essential requirements and other relevant provisions of 
Directive 89/106/EEC a 2004/108/EC.  The original of the conformity assessment 
can be found at 

www.jablotron.com

 - Technical Support section

Note:

 Although this product does not contain any harmful materials 

we suggest you return the product to the dealer or directly to the 
producer after use. For more detailed information visit 

www.jablotron.com

.