The AC-160-DIN Wireless multipurpose relay for DIN rails
The AC-160-DIN wireless multipurpose relay for DIN rails
2 / 2
MLZ54301
published for downloading, file type *.fwp). If Automatic updates
are enabled, the FW pack will be selected automatically.
7. F-Link shows a window with a device listing, select USB.
8. Then press
OK
and perform the upgrade for the selected device
(the relay).
9. Disconnect the cable and attach the relay front cover.
10. Check the settings via the
F-Link
software
.
Note:
The MicroUSB cable (required for FW upgrade) is not supplied
with the MFR.
Stand-alone mode
Up to 64 one-way communicating detectors of the JA-15x series
and keyfobs of the JA-15xJ MS and JA-16xJ series can be enrolled
in the MFR. EnrollmentEnrolment and setup of the detector and keyfob
modes is done by the Learn/Set button (3). The relay can recognize
3 lengths of pressing:
Short press < 3 s
Turns the relay ON or scrolls the menu
Long press > 3 s < 6 s
Enters the menu or sends an enrollment
signal
Very long press 6 s
Exits the menu or confirms the timer
Enrolling the detectors and keyfobs
First of all select the mode in which the device should be operated
and then enroll it.
Procedure:
1. Perform a long press of the Learn/Set button (3) until the yellow
LED starts flashing.
2.
When you release the button the relay is ready to receive
an enrolling signal from a device, confirmed by permanent lighting
of the yellow LED and a flashing red LED. The number of flashes
determines the operation mode to which the device will be enrolled.
Operation mode selection is done by repeatedly briefly pressing
the button.
No. of red LED flashes.
Mode
1x * * * *
Copy (extended
with detectors)
Switch on /Switch off
(with keyfobs)
2x ** ** ** **
Impulse
3x *** *** ***
Change status
4x **** ****
Always switches off
5x ***** *****
Block
1x longer lit, short pause
Mode for deleting detectors
Note:
Extended copy and Impulse – minimum switching time is 1s
3. Enrolling a detector - Insert the batteries into the detector – it sends
an enrollment signal.
4. Enrolling a keyfob – long press of a selected button – The MFR
will react to this button being pressed. Each button can be
individually enrolled to the MFR’s positions. A 4-buttton keyfob
can take 4 MFR positions with different relay switching modes.
Enrolling by pressing a pair of buttons at the same time is possible;
5. Enrolling is confirmed by alternate flashing of the LED in red
and green.
6. When the enrollment procedure has been done correctly, the MFR
goes back to its normal operating mode – the green LED is ON.
If you want to enroll the next device you must repeat the whole
enrollment procedure.
Erasing a device
1. Perform a long press of the Learn/Set button (3) until the yellow
LED starts flashing. Now release the button and the yellow LED
indicates permanently and the red LED flashes.
2. By repeated pressing (5x) of the button (3) select the mode
when the red LED lights and regularly fades out.
3. Insert the batteries into the detector or long-press a keyfob
button which is to be erased from the MFR.
4. Erasing a device from the MFR is confirmed by alternate
flashing of the red / green LED indicators.
5. When the erasing procedure has been finished, the relay goes
back to its normal operating mode.
Note: Erasing is also possible by deleting a production code
in the internal settings of the MFR located in the F-
/LQNVRIWZDUH
Common timer setup
1. Perform a long press of the Learn/Set button (3) until the yellow
LED starts flashing. Now release the button. The yellow LED
indicates permanently and the red LED flashes.
2. Perform a long press of the Learn/Set button (3) again until
the flashing of the red LED changes to permanent lighting of the
green LED.
3. When the button is released the green LED will start flashing.
The number of flashes determines the pre-set period
of the Common timer.
By repeated pressing of the button (1) select the required time
of the common timer. The table shows 5 default options.
Those values cannot be changed in stand-alone mode. When it is
pre-set by F-Link to a different time (not to predefined/default
values), the green LED lights and regularly fades away.
No. of green LED flashes.
Timer period
1x * * * *
1 s (default)
2x ** ** ** **
1 min
3x *** *** ***
3 min
4x **** ****
15 min
5x ***** *****
30 min
1x longer lit, short pause
Different settings (via F-Link)
4. Confirm the selected value by pressing the button for more than 6 s
until the red/green LED indicators start flashing. Settings are saved.
Note
: No activity for longer than 1 minute terminates
the setup/enrollment mode, saves the changes and goes to normal
operating mode.
Operation status - optical indication
LED indication
Mode
ERR
(yellow)
OFF
Everything OK
ON
(stand-alone mode)
Setting
ON
(operation with control
panel)
Loss of
communication
or
Internal settings
entered
Flashes 1/s
Low battery in one of
the devices
RELAY
(red/green)
RED LED ON
Relay ON
GREEN LED ON
Relay OFF
GREEN flashes 4/1
Blocking when OFF
GREEN/RED
flashes 4/1
Blocking when ON
Resetting the relay
A full relay reset and complete erasing of all enrolled devices
is performed by pressing the button for more than 6 s (3). It is indicated
with the alternate flashing of red/green of the ‘RELAY’ LED
simultaneously with a permanently lit ‘ERR’ LED. The Learn/Set button
must be then released within 3 s and then (also within 3 s) briefly
pressed again. The MFR reset is confirmed by quick alternate flashing
in red/green of the ‘RELAY’ LED with a yellow ‘ERR’ LED. After this only
the green and yellow LED stays lit. Resetting doesn´t erase an enrolled
control panel which is currently in service mode (in this case the yellow
LED will not be lit).
Technical specifications
Operational power
230 V/50 Hz
Own power consumption for 230 V AC (min / max)
0.5 W/1.7 W
Communication band
868.1 MHz, Jablotron protocol
Antenna
Internal/optional external antenna type AN-868
MFR Contact rating - protection class II:
- Maximum switching voltage
250 V AC
-
5HVLVWLYHORDGFRVij
max.16 A
-
,QGXFWLYHFDSDFLWLYHORDGFRVij
max.
8 A
- Halogen lights
max. 1000 W
- Minimum switching DC power
0.5 W
Recommended connection wires:
max. 2 x 1.5 mm
2
; max. 1 x 2.5 mm
2
IP covering
IP-20 (according to EN 65529), IP-40 (with a front panel)
Dimensions
18 x 90 x 64 mm
Weight
65 g
Operational temperature range
-10 to + 40°C,
relative humidity 75% no condensation
Complies with
ETSI EN 300 220-1, EN 50130-4
EN 55022, EN 60950-1, EN 50581
Can be operated to
ERC REC 70-03
JABLOTRON ALARMS a.s. hereby declares that the AC-160-
DIN is in a compliance with the relevant Union harmonisation
legislation: Directives No: 2014/53/EU, 2014/35/EU,
2014/30/EU, 2011/65/EU. The original of the conformity
assessment can be found at www.jablotron.com - Technical
Support section.
Note: Although this product does not contain any harmful
materials we suggest you return the product to the dealer
or directly to the producer after use
.