
PR_I020/2023-08-11-EN
Revision: 5
7
Installation
If this room heater is not properly installed, a house fire may
result. To reduce the risk of fire, follow the installation
instructions. Contact local building or fire officials about
restrictions and installation inspection requirements in your
area.
WARNING ALWAYS USE J.A. ROBY PARTS on your
appliance. Using other differences parts can damage the
appliance and cause injury.
Use of smoke detectors and carbon
monoxide monitors
To provide reasonable fire prevention, the following should be
given serious consideration:
1. At least one smoke detector on each floor of your home
should be installed to ensure your safety. They should be
located away from the heating appliance and close to the
sleeping areas. Follow the smoke detector manufacturer’s
placement and installation instructions and be sure to
maintain regularly.
2. A conveniently located Class A fire extinguisher to contend
with small fires resulting from burning embers.
3. A CO detector should be installed in the room with the
appliance.
4. A practiced evacuation plan, consisting of at least two
escape routes.
5. A plan to deal with a chimney fire as follows:
a. In the event of a chimney fire:
b. Evacuate the house immediately
c. Notify fire department.
The average of the CO emission (carbon monoxide) is 68.5
g/hr
. To maintain this rate, it’s recommended to operate the
appliance in low or medium burn rate.
The hazards with some fuels (e.g. Charcoal) and possibilities
of generating carbon monoxide and the hazards from carbon
monoxides.
When the smoke detector is activated is mean that the
smoke spill out of the appliance. Verify the door is close
and the draft in chimney is good.
Floor protection
Your stove must be installed on a non-combustible material
plate to protect the floor and avoid fire which would be caused
by:
•
Projections of sparks when door opening or loading
logs;
•
The heat radiation when stove runaway should have an
ignition to the floor and the coating;
•
Flow of creosote when there is a chimney fire.
The coating used must be non-combustible and approved
according to standard or your local codes (Example: cement,
brick, ceramic tiles…)
Floor protection plate minimum
dimensions
The following dimensions are the minimums values and they
can be greater.
Canada:
•
44 ¾ (113.73 cm)
•
53 ¾ (136.53 cm)
•
3/8 in thickness (1 cm)
Clearances chart on floor plate
The following dimensions are the minimums values and they
can be greater.
Canada:
•
8 inches (20.32 cm) rear
•
8 inches (20.32 cm) side
•
18 inches (45.72 cm) loading door
Содержание ULTIMATE TOR 2015
Страница 4: ...PR_I020 2023 08 11 EN Revision 5 4 Rating plate...
Страница 5: ...PR_I020 2023 08 11 EN Revision 5 5 Appliance Dimension...
Страница 13: ...PR_I020 2023 08 11 EN Revision 5 13 Firebox configuration and part list...
Страница 28: ...PR_I020 2023 08 11 EN Revision 5 28 Annex 1 Door assembly Square Door Arc Door...
Страница 29: ...PR_I020 2023 08 11 EN Revision 5 29 Annex 2 Circuit diagram of fan Snap Disc Box parts description...