Technology Description-
Centrifugal blower and filter housing assembly with electric motor. Filtered air intake, distributes
air inside tank for ventilation of tank head space, designed to evacuate volatilized THM’s, gases and other contaminants
from the head space.
Figure 1:
F8 Blower
Electrical Requirements -
Requires 480VAC three-phase, 60Hz power. Ixom recommends secondary disconnect
to be located near blower equipment. For three-phase motors, three-phase motor protection is recommended.
All
conduit, conductors, switches, breakers, emergency stop buttons, control panels and other controls shall be installed in
accordance to all NEC, State, and local regulations. (Not supplied by Ixom.)
Subject to change without notice.
Maintenance / Warranty
- Limited maintenance. Limited 2-year warranty. See GridBee THM Removal Systems Limited
Replacement Warranty for more details.
Air Filters
- Six Filter Elements, 98%+ removal efficiency to
10 micron, synthetic felt air filter. Each rated for 3000 CFM
(85 m
3
/min), 30ft
2
surface area, washable, galvanized steel
reinforcement frame Dimensions: 24” X 24” X 2”
Replacement Filters PN: 20012066
Mounting -
Ground mount or roof mount configurations available.
Wiring -
4-conductors required (L1, L2, L3, Gnd). Electrical TEFC motor wiring box for conduit connection and
electrical splicing. Multiple locations available for conduit entry through air filter housing.
Motor -
3HP Baldor TEFC, wash down duty induction motor, designed for continuous operation, low power
requirement, direct drive, no gearbox and no lubrication schedule required. No heater.
Materials of Construction
- T316 stainless steel, with gray
epoxy or powder coating.
Air Flow Rate
- 3000 cubic feet per minute (85 cubic meters
per minute) at 4” (10 cm) of H
2
O. Tank gravity vents must al-
low for 240 sq-inch (after screens and mesh) minimum open
surface area per blower.
Shipping Size / Weight
• Crate -
86in x 86in x 64in (2.2 m x 2.2 m x 1.6 m) / 1500 lbs (680 kg).
Exact weight and dimensions may vary
dependent on blower and roof mount configuration.
Vibration Isolation
- Secured to T316SS skid, separated by
rubber isolation pads properly sized for blower weight and
operation.
Coupling and Bearings -
Double supported fan wheel using quality Baldor Dodge pillow block bearings and
coupling.
Part Number
- 100716
Duct Sizing Requirement
- Ø 18” minimum or equivalent
open space. (Ø 24” recommended.)
© 2020 Ixom | www.medoraco.com | 866 - 437 - 8076 | [email protected]
Technical Data Sheet
F8 Ventilation Blower
2030_10194_20200804
O&M_F8_10335_20201026a - 4