iWorX® ALM2
505-013, Effective: November 12, 2010
15
© 2010 Taco Electronic Solutions, Inc.
Outputs
This screen displays the current values of the ALM2’s outputs. These values cannot be changed from this screen. The
default name for each configured output is
Output #X
, where X is the output reference number that was configured for
the given output.
Configuration
All Settings
This screen displays the settings used by the controller.
Output
Range
Description
Output #1
Off, On
Status of each alarm output.
Output #2
Output #3
Output #4
Output #5
Output #6
Output #7
Output #8
Setting
Range
Default
Description
Hysteresis
0.0 to 9.0
°F
(0.0 to 5.0
°C)
0.9
°F
(0.5
°C)
Amount of hysteresis used during
thermistor data comparisons.
Input #1 Lo Limit
-29.9 to 230.0
°F
(-34.4 to 110.0
°C)
32.0
°F
(0.0
°C)
Threshold temperature below
which the controller will report a
temperature alarm.
Input #2 Lo Limit
Input #3 Lo Limit
Input #4 Lo Limit
Input #5 Lo Limit
Input #6 Lo Limit
Input #7 Lo Limit
Input #8 Lo Limit
Input #1 Hi Limit
-29.9 to 230.0
°F
(-34.4 to 110.0
°C)
50.0
°F
(10.0
°C) Threshold temperature above
which the controller will report a
temperature alarm.
Input #2 Hi Limit
Input #3 Hi Limit
Input #4 Hi Limit
Input #5 Hi Limit
Input #6 Hi Limit
Input #7 Hi Limit
Input #8 Hi Limit
Input #1 Type
Disabled,
Thermistor,
Switch
(Open),
Switch
(Closed)
Disabled
Operating mode for each input. For
switch inputs, the word in paren-
theses indicates the normal state
of the switch.
Input #2 Type
Input #3 Type
Input #4 Type
Input #5 Type
Input #6 Type
Input #7 Type
Input #8 Type