Precautions for use
•
Electrical work should be performed by a qualified opera-
tor. Otherwise, personal or property damage accident may
result.
• Do not install the pump in the following places where...
–Under a flammable atmosphere or in a dusty/humid place.
–Under direct sunlight or wind & rain.
–
Ambient temperature exceeds 40ºC or falls below 0ºC.
Protect the pump with a cover when installing it out of
doors.
•
Select a level location where is free from vibration and liq-
uid can't stay. Anchor the pump with M5 bolts so as not to
vibrate. If the pump is installed at a tilt, a flow may reduce.
•
When two or more pumps are installed, the pump opera-
tion interacts each other and vibration becomes significant,
resulting in poor performance or failure of internal electri-
cal devices. Select an installation location where tolerates
vibration to enough degree.
•
Keep an ample working area around the pump for inspec-
tion and maintenance.
• Install the pump as close to a supply tank.
•
Install the pump in a cool and dark place when handling
liquids that readily generate gas bubbles such as sodium
hypochlorite or hydrazine solution. Flooded suction applica-
tion is strongly recommended for these liquids.
Precautions for use