Commissioning
AirModule 6 720 813 268(2014/10)
40
11.3
Commissioning other settings
If some functions are not activated, and modules, units or components
are not installed, the non relevant items are hidden, while other settings
are selected.
11.3.1 Checklist: adjust settings according to customer
requirements
When commissioning a device, ensure the satisfaction of both parties,
making sure that the heating system meets the customer's needs and will
not give cause for complaints. In our experience, the following settings
are very important for the satisfaction of the system user:
▶ Adjust other settings in the main menu according to the customer's
requirements (
Operating instructions).
11.3.2 Important system settings
The service menu settings must under all circumstances be checked and
if necessary modified during commissioning. Otherwise the system
function cannot be ensured. It is best to check all displayed settings. It is
possible that the set values must be verified by the system user, e.g. the
cooling settings.
11.4
Performing the function test
The function test is located in the Diagnostics menu. The available items
depend on the installed system. In this menu, you can test e.g. the:
DHW
circulation pump
:
On
/
Off
(
11.5
Check monitored values
Monitored values are shown in the
Diagnosis
menu (
11.6
System handover
▶ Ensure that there are no temperature restrictions for heating and
DHW set on the heat pump module. Otherwise the user interface
cannot control the DHW or flow temperature.
▶ Explain to the customer how the user interface and the accessories
work and how to operate them.
▶ Inform the customer about the selected settings.
Menu Item
Customer requirements/settings
Control type
Outside temp. compensated (
Adjusting the heating curve
Adjust the heating curve (
displayed heating curve applies to a room
temperature of 21 °C.
Building type (adjustment)
Light, Medium, Heavy (
Operating mode
Adjust the standard settings/own time
program according to the customer's
requirements (
User interface operating
instructions).
Table 22 Checklist: important settings identify customer requirements
If relative humidity is not measured in a cooled room
(e.g. with a CR10H), condensation might form. In this
case, it is required to set the minimum flow temperature
to a suitable value to prevent condensation.