iVS Range Installation and Operating Manual 

This document provides necessary information for the installation and commissioning of the iVS A to D Range 
Failsafe quarter-turn electric actuator. Each unit is shipped from the factory with initial calibration of cams and 
switches completed for 0° 

 90° operation. However, these are general settings and serve as a starting point for 

proper calibration of the actuator in its real-world application. 

Only competent and trained personnel should install, maintain and operate iVS actuators.  Any work related to 
an actuator must be carried out in accordance with this manual, accompanied manuals, and related codes and 
regulations. Local workplace health and safety rules should always be followed. 

NOTE: Throughout the documentation we reference CLOCKWISE (CW)

 

rotation (spring retracted) as moving in 

the  CLOSE  direction  and  COUNTER-CLOCKWISE  (CCW)  rotation  (spring  compressed)  as  moving  in  the  OPEN 
direction. 

Receiving / Inspection 

 

Carefully inspect for shipping damage. Damage to the shipping carton is usually a good indication that it has 
received rough handing. Report all damage immediately to the freight carrier and your seller.

 

 

After unpacking the product and information packet, please take care to save the shipping carton and any 
packing material, in case of product return or replacement. Verify that the item on the packing list or bill of 
lading is the same as your own documentation. If there is any discrepancy, please contact the seller.

 

Storage 

 

If the actuator cannot be installed immediately, store it in a clean, dry environment. The actuator must be 
protected from excess moisture and dust, until you are ready to connect the electrical cables. The actuator 
should not be installed outside, unless it is powered up and has the proper conduit connections.

 

 

If the actuator must be installed, but cannot be wired, do not remove the plastic cable entry plugs. When 
the actuator is wired, it is recommended to replace the plastic cable entry plugs with water-proof conduit 
fittings.

 

 

Storage temperature should be within the standard operating temperature range of the actuator.

 

 
 

 

Содержание IVS A

Страница 1: ...Receiving Inspection Carefully inspect for shipping damage Damage to the shipping carton is usually a good indication that it has received rough handing Report all damage immediately to the freight c...

Страница 2: ...ate between 0 and 90 Most failsafe quarter turn products will not require recalibration of these settings If any travel adjustment is necessary please refer to the Limit Switch Setting section below 2...

Страница 3: ...Commissioning section below 12 Check below explanation of Duty Cycle The intended service should not go above the maximum duty cycle as noted on the actuator nameplate Installation Notes These actuat...

Страница 4: ...ide gearbox if supplied compresses the spring as the valve is opened See Photo 4 The unit is shipped without the handwheel assembled as shown in Photo 5 Using the hardware provided thread the socket h...

Страница 5: ...ctrical travel limiting device The mechanical end stop MUST always be set before the limit switch settings Ensure that the power is OFF Locate the housing cap see Photo 8 and remove the cap screws usi...

Страница 6: ...he open and closed position of the valve The position is set to stop the travel of the actuator when the travel cams activate the limit switch Standard is two limit switches LS1 LS2 one for open one f...

Страница 7: ...set screw on cam TC2 o Rotate cam counter clockwise to reset the switch contact o Then slowly rotate cam clockwise until a light click is heard o Securely tighten the cam and apply power to check the...

Страница 8: ...oosen the set screw on cam TC4 o Rotate cam counter clockwise to reset the switch contact o Then slowly rotate cam clockwise until a light click is heard o Slowly continue to rotate in the same direct...

Страница 9: ...than specified New valve may be required The voltage may be under over rated Check the supply voltage The actuator may be against one of the mechanical end stops Reset limit switches and adjust end s...