8. Complete parameter lists
8.1 Menu – ”Status”
Parameters displayed in the Status menu are only readable.
Parameter
Range
Description
Setp. Main
-30 - +80
°
C Display actual main setpoint
Setp. Supply air
-30 - +80
°
C Display actual supply setpoint
Outdoor air
-30 - +80
°
C Display actual outdoor temperature
Supply air
-30 - +80
°
C Display actual supply air temperature
Room/Extract air
-30 - +80
°
C Display actual room/extract air temp.
Freeze guard
-30 - +80
°
C Display actual heater temperature
Heat
0 – 100%
Display actual heater output
Rot. VVX
0 – 100%
Display actual recovery output
Cool
0 – 100%
Display actual cooler output
SA
0 – 100%
Display actual supply air fan output
EA
0 – 100%
Display actual exhaust air fan output
8.2 Menu – ”SETUP”
In Setup menu are all configurations made.
Parameter
Range
Description
Default
Meny/Menu
Svenska/English
Selection of language.
Svenska
Config. heat
El/Water
Selection of a water or an electrical heater Water
CP heat
Exesice/Cont.operation Selects if pump should operates
continuously or if it should stop during
summer.
Exercise
Cool battery
Not installed/Installed
Select if a cooler is to be controlled.
Not installed
CP cool
Exercise/Cont.operatio
n/DX cool
Circulation pump, run at needs with
exercise.
Circulation pump, continuous run.
DX-cooler controls on/off by digital output.
Exercise
Config. VVX
Digital/Analog
Selection if VVX is to be controlled by an
analogue (o.10V) or a digital output.
Digital
Night cooling
Not installed/Installed
Select if night cooling is to be used.
Not installed
Night heating
Not installed/Installed
Select if night heating is to be used.
Not installed
Regulation
Supply air reg./
Exhaust air regl./
Room reg./
Climate dep. reg
Supply air control
Extract air control (cascade)
Room control (cascade)
Extract air cascade (summer), Supply air
(winter)
Supply air
reg.
Cool recycl.
Not installed/Installed
Select if chill recovery is to be used in
cooling sequence.
Not installed
Config. AUX
ALARM B/ALARM
A/STOP
AUX sets an A-alarm and unit stops.
AUX sets an B-alarm, unit operates as
usual.
Emergency stop, unit stops, no overrun
time of fans.
ALARM B
Delay AUX
0-60 min
Delay before an A or B-alarm is set up.
Not used at emergency stop.
3 min
Delay Fan Alarm
0-60 min
Time delay in IVC3 before a B-alarm is set
of and unit stops.
3 min
Manual operation
Off/On
Make outputs available for manual overrun Off