background image

 

IV Produkt Control Unit IVC3 

 

IVC3 Basic Manual 2004-12-15.doc 

16/18 

8. Complete parameter lists 

 

8.1  Menu – ”Status” 

 

Parameters displayed in the Status menu are only readable. 

 

Parameter 

Range 

Description 

Setp. Main 

-30 - +80

°

C  Display actual main setpoint 

Setp. Supply air 

-30 - +80

°

C  Display actual supply setpoint 

Outdoor air 

-30 - +80

°

C  Display actual outdoor temperature 

Supply air 

-30 - +80

°

C  Display actual supply air temperature 

Room/Extract air 

-30 - +80

°

C  Display actual room/extract air temp. 

Freeze guard 

-30 - +80

°

C  Display actual heater temperature 

Heat 

0 – 100% 

Display actual heater output 

Rot. VVX 

0 – 100% 

Display actual recovery output 

Cool 

0 – 100% 

Display actual cooler output 

SA 

0 – 100% 

Display actual supply air fan output 

EA 

0 – 100% 

Display actual exhaust air fan output 

  

8.2  Menu – ”SETUP” 

 

In Setup menu are all configurations made.  

 

Parameter 

Range 

Description 

Default 

Meny/Menu 

Svenska/English 

Selection of language. 

Svenska 

Config. heat 

El/Water 

Selection of a water or an electrical heater  Water 

CP heat 

Exesice/Cont.operation  Selects if pump should operates 

continuously or if it should stop during 

summer.   

Exercise 

Cool battery 

Not installed/Installed 

Select if a cooler is to be controlled.   

Not installed 

CP cool 

Exercise/Cont.operatio

n/DX cool 

Circulation pump, run at needs with 

exercise. 

Circulation pump, continuous run. 

DX-cooler controls on/off by digital output. 

Exercise 

Config. VVX 

Digital/Analog 

Selection if VVX is to be controlled by an 

analogue (o.10V) or a digital output. 

Digital 

Night cooling 

Not installed/Installed 

Select if night cooling is to be used.  

Not installed 

Night heating 

Not installed/Installed 

Select if night heating is to be used. 

Not installed 

Regulation 

Supply air reg./ 

Exhaust air regl./ 

Room reg./ 

Climate dep. reg 

Supply air control 

Extract air control (cascade) 

Room control (cascade) 

Extract air cascade (summer), Supply air 

(winter) 

Supply air 

reg. 

Cool recycl. 

Not installed/Installed 

Select if chill recovery is to be used in 

cooling sequence. 

Not installed 

Config. AUX 

ALARM B/ALARM 

A/STOP 

AUX sets an A-alarm and unit stops. 

AUX sets an B-alarm, unit operates as 

usual. 

Emergency stop, unit stops, no overrun 

time of fans. 

ALARM B 

Delay AUX 

0-60 min 

Delay before an A or B-alarm is set up. 

Not used at emergency stop. 

3 min 

Delay Fan Alarm 

0-60 min 

Time delay in IVC3 before a B-alarm is set 

of and unit stops.  

3 min 

Manual operation 

Off/On 

Make outputs available for manual overrun  Off 

 

Содержание IVC3

Страница 1: ...IV Produkt Control Unit IVC3 IVC3 Basic Manual 2004 12 15 doc Basic Manual IVC3 Control System Rev 1 0 ...

Страница 2: ...ht cooling extract air temperature sensor 9 2 10 2 Night cooling room temperature sensor 9 2 10 3 General conditions for night cooling 9 2 10 4 Night cooling settings 9 2 11 Night heating 10 2 11 1 Night heating extract air temperature sensor 10 2 11 2 Night cooling room temperature sensor 10 2 11 3 General conditions for night heating 10 2 11 4 Night heating settings 10 2 12 Limited airflow 10 2 ...

Страница 3: ...nd outputs 14 7 1 Digital output relay 14 7 2 Digital output triac 15 7 3 Analogue output 0 10VDC 15 7 4 Analogue input passive sensor 15 7 5 Digital input from free contacts 15 8 Parameter lists 16 8 1 Menu Status 16 8 2 Menu Setup 16 8 3 Menu Settings 17 8 4 Menu Clock 18 9 Communications 18 ...

Страница 4: ...mal speed Unit operates with SA and EA at forced speed Unit operates with fan speed according to time schedule 2 3 Fan speed normal and forced Four different operation modes can be set STOP NORMAL FORCED and AUTO Settings Setting Description SA normal 0 100 SA peed at normal speed EA normal 0 100 EA peed at normal speed SA forced 0 100 SA peed at forced speed EA forced 0 100 EA peed at forced spee...

Страница 5: ...ing unit Circulation pump for warm water configures for either exercise or continues operation If exercise are selected the pump will stop when outdoors temperature exceeds set limit Temp pump stop plus a 2 hysteresis pump will start when outdoor temperature decrease set limit The pump will always start if valve opens Pump run are off delayed 4 minutes Pump exercises one minute once a day when sto...

Страница 6: ...art and stop parameters for DX cool are to be set in parameter menu DX cool start DX cool stop DX cooler are start delayed 2 minutes Heat recovery is delayed 2 minutes after a cooling sequence Setup Setting Description Cool battery Not installed Installed Select if a cooler is to be controlled CP cool Excesice Cont operation DX cool Circulation pump run at needs whit exercise Circulation pump cont...

Страница 7: ...ain setpoint extract air temperature Min Supply air 0 60 C Minimum supply air temperature Max Supply air 0 60 C Maximum supply air temperature 2 8 3 Room control Constant room temperature with min and max limits for supply air Room temperature sets set point for supply air to maintain a constant extract air temperature Cascade factor 5 Settings Setting Description Setp Main 0 60 C Main setpoint ro...

Страница 8: ... fan forced 30 30 C See fig above 2 9 Control sequence Cooler heat recovery VVX and heater will in sequence control the temperature At warming demand the output to cooler decreases than VVX starts with different run stop intervals out of needs at digital VVX or with an increasing output signal at analogue VVX and finally increased output signal to heater The sequence is opposite at cooling request...

Страница 9: ...A Cooler recovery and heater are always blocked during night cooling 2 10 2 Night cooling room temperature sensor Controller measures continuously room temperature to decide if night cooling is needed If room temperature exceeds set start limit Night cooling start the unit will start for night cooling until room temperature are more than 1 below start point Unit will in night cooling run on forced...

Страница 10: ...t is selectable in operating terminal if EA are to be used in night heating EA night heating Ordinary temperature set points are used in night heating 2 11 2 Night heating room temperature sensor Controller measures continuously room temperature to decide if night cooling is needed If room temperature drops below set start limit Night heating start the unit will start for night heating until room ...

Страница 11: ...this point there is no compensation Outd comp summer Temp 2 30 30 C Setpoint for full summer compensation at this point compensation has is full influence on temp control Outd comp summer Comp 30 30 C The value that compensation would achieve at Temp 2 summer Outd comp winter Temp 1 30 30 C Setpoint for full winter compensation at this point compensation has is full influence on temp control Outd ...

Страница 12: ...it stops 3 4 Alarm pump overheating Alarm activates by fault indication from pump or if electrical heater indicates overheating Alarm at closed contact Alarm is set by a closing external contact Result water heater alarm category B unit stops if heater valve are opened unit operates as usual if heater valve are closed Result electrical heater alarm category B unit operates as usual electrical heat...

Страница 13: ... alarm and unit operates as usual No alarm would be set up at a unit without cooler if outdoor temperature exceeds 20 C Settings Setting Description Alarm temp fail 0 60 C Deviation limit from setpoint for supply air temperature a B alarm is set up after more than 30 minutes deviation An A alarm is set up and unit stops if temperature drops more than 5 below low limit 4 Time schedule At Fan mode s...

Страница 14: ...n an output is manually set Only configured outputs are enable for manual overrun Not configured outputs are hidden or displayed not installed Settings Setting Description SA man 0 100 Supply air fan manual overrun output value EA man 0 100 Exhaust air fan manual overrun output value Rot VVX man 0 100 Revolving heat recovery manual overrun output value H valve man 0 100 Heater valve manual overrun...

Страница 15: ...ving heat recovery VVX 230 VAC 7 3 Analogue output 0 10 VDC 1 Heater 2 Cooler 3 Supply Air fan SA 4 Exhaust Air fan EA 5 Heat recovery VVX 7 4 Analogue input passive sensor 1 Supply air temperature 30 C 80 C 2 Outdoor air temperature 30 C 80 C 3 Freeze protection temperature 30 C 80 C 4 Exhaust air room temperature 30 C 80 C 7 5 Digital input from free contacts 1 Alarm fans 2 Extended operation in...

Страница 16: ...rcise Cool battery Not installed Installed Select if a cooler is to be controlled Not installed CP cool Exercise Cont operatio n DX cool Circulation pump run at needs with exercise Circulation pump continuous run DX cooler controls on off by digital output Exercise Config VVX Digital Analog Selection if VVX is to be controlled by an analogue o 10V or a digital output Digital Night cooling Not inst...

Страница 17: ...its to normal speed at outdoor temp below set value Climate adapted control Low outdoor temperature fan speed normal at and below this point See fig 25 C 0 C Outd Temp fan forced 30 30 C Only at Climate adapted control High outdoor temperature fan speed forced at and above this point The point where controller shift between supply and extract air control See fig 14 C Outd comp summer Temp 1 30 30 ...

Страница 18: ... be used at night heating Start SA man 0 100 Supply air fan manual overrun output value 0 EA man 0 100 Exhaust air fan manual overrun output value 0 Rot VVX man 0 100 Revolving heat recovery manual overrun output value 0 H valve man 0 100 Heater valve manual overrun output value 0 C valve man 0 100 Cooler valve manual overrun output value 0 El heater man 0 100 Electrical heater manual overrun outp...

Отзывы: