Product sheet

Operation and Maintenance

Flexomix EXP

2015-01-07

IV Produkt’s continuous product development may give rise to specification changes without prior notice.

1 (2)

Integral attenuation (dB)

Octave band  

intermediate 

frequency (Hz)

63

125

250

500

1,000

2,000

4,000

8,000

Damping (dB)

6

7

6

5

7

10

15

18

Plate heat exchanger (code EXP)

The EXP plate heat exchanger is a complete unit with a 

plate exchanger which uses heat transfer according to 

the air-air principle.

The purpose of the heat exchanger is to recover heat 

from the extract air and transfer this heat to the supply 

air.  

This reduces the output required and the energy use.

The heat exchanger is a cross-flow unit constructed 

from aluminium plates which are also available with an 

epoxy finish. Smooth ducts in the direction of airflow 

provide a low pressure drop and minimal risk of dust 

building up.

A faulty heat recovery function through reduced recov-

ery efficiency entails increased energy use. This also 

means that the planned supply air temperature will not 

be attained when outdoor temperatures are low. 

Possible reasons for reduced recovery efficiency could 

be the fouling of the heat-exchanging surfaces, the 

bypass damper not closing completely, or the extract 

air filter being dirty.

At low temperatures the extract air humidity is precipi-

tated. The condensate is collected in a drip tray with a 

drainage connection. The humidity precipitation also 

means there is a risk of ice forming in the exchanger. 

The formation of ice is counteracted by some of the 

outdoor air flow being bypassed past the exchanger.

Particular attention should be paid to any ice forming 

in the extract air section of the heat recovery unit. If 

operation problems caused by ice forming occur, the 

function of the frost protection equipment on the heat 

recovery unit should be checked.

The bypass and shut-off dampers are of KJS type in 

tightness class 2 in accordance with SS-EN1751 (VVS 

AMA-98) and corrosion class C4 in accordance with 

SS-EN ISO 12944-2.

Technical data, sizes 060–600

Configuration

Drainage

Connection = Ø 20 mm

Damper

1 damper motors are required (damper shaft 12×12 mm).

Size

Required torque (Nm)

060, 100

3

150

4

190, 240, 300

5

360

6

480, 600