Operation Manual -
PoWerMaster®
2400 – 30 - 90 kVA
Trouble Shooting & Repair
Document no. 578.650BB
Page 65 of 91
Continued from previous page
Error code
Error text in display
Help text
1st. Corrective action
6001
EF OUTPUT 1 RIPPLE TOO HIGH
Ripple Voltage Exceeded Limit
6002
EF OUTPUT 2 RIPPLE TOO HIGH
Ripple Voltage Exceeded Limit
6101
CABLE 1 TEMPERATURE TOO HIGH
6102
CABLE 2 TEMPERATURE TOO HIGH
6201
NEUTRAL CONDUCTOR RUPTURE OUTPUT 1
6202
NEUTRAL CONDUCTOR RUPTURE OUTPUT 2
6301
EF SIGNAL DROP OUT - OUTPUT 1
EF Signal Disappeared at Output 1
6302
EF SIGNAL DROP OUT - OUTPUT 2
EF Signal Disappeared at Output 2
6003
EF SIGNAL DROP OUT – 28 V OUTPUT
EF Signal Disappeared at 28 V Output
7000
OUTPUT VOLTAGE TOO HIGH
Voltage > 32V - 4s
7100
OUTPUT VOLTAGE TOO HIGH
Voltage > 40V – 150 ms
7200
OUTPUT VOLTAGE TOO LOW
Voltage < 20V - 4s
7300
SHORT CIRCUIT AT 28V OUTPUT
>75kW
Press start to reset
7400
28V OUTPUT CURRENT TOO HIGH
7500
28V RECTIFIER TEMP TOO HIGH
8000
ACR SUPPLY VOLTAGE MISSING
8001
ACR ERROR
8100
CABLE COIL / VFD ERROR
Check Cable Coil, VFD & Motor
8200
COIL WINDING TIME-OUT
Coil Winding Exceeded 50 s
8300
FAULT – CABLE HANDLING SYSTEM
9000
END OF FACTORY TEST
9100+code
PLUG & PLAY FAILED - OUTPUT X
9200+code
PLUG & PLAY COMPLETED - OUTPUT X
List below shows the complete list of error codes and next corrective actions:
Error code
2nd. Corrective action
3rd. Corrective action
4th. Corrective action
0
100
200
Replace Control Board A1
201
Verify ID Chip inserted
Contact ITW GSE
202
250
300 - 301
Check input voltage
Check Q4 & G1
350
Check wires attached to X1 (X2 /X3)
400
Check emergency stop
Check user EPO (A2:X14)
Replace Control Board A1
500
Replace Control Board A1
600
Replace Control Board A1
700
Replace battery
750
Check / Set to current time and date
800
Check input voltage
Replace Control Board A1
Replace Interface Board A2
900
Check input voltage
Replace Control Board A1
Replace Interface Board A2
1000
Check input voltage
Check DC softstart charging voltage
> 400 V
Replace Interface Board A2
Replace Capacitor Module A5
Replace Control Board A1
1100
Check input voltage
Check Q5
Replace Control Board A1
Replace Interface Board A2
1200
1201
Check input voltage
Replace Control Board A1
Replace Interface Board A2
1202
Check input voltage
Replace Control Board A1
Replace Interface Board A2
1300
Check DC sharing voltage at R1
Replace Control Board A1
Replace Interface Board A2
1400
Check input voltage
Check equal voltage across V1 – V6
Replace Control Board A1
Replace Interface Board A2
1450
Check input voltage
Check equal voltage across V1 – V6
Replace Control Board A1
Replace Interface Board A2
Table continues on next page