
6
USER MANUAL SPIKA
2) Pipe diameter:
MS-500: liquid 1/4” – discharge 3/8”
MS-1000: liquid 5/16” – discharge 1/2”
3) Line connection:
MS-500 3/8” – 3/8” SAE
Condenser 1/4” – 3/8” ODS
MS-1000 3/8” – 1/2” SAE
Condenser 5/16” – 1/2” ODS
4) The pipeline length will be 16ft (5m) maximum. To increase the pipeline length, see point 9.2
Locate the condenser as near as possible to the ice machine. Remote condenser location must not exceed any of the
following limits:
1) Maximum drop from the ice making head to the remote condenser: 16.4 physical ft (5 meters).
2) Maximum rise from the ice making head to the remote condenser: 35 physical ft (11 meters).
3) Maximum pipelines length: 100 physical ft (30 meters).
4) Maximum calculated pipelines length: 150 ft (45 meters).
Calculated pipeline length = Drop + Rise + Horizontal distance ≤ 150 ft (45 meters)
Drop = DD x 6.6
(DD = distance in feet)
Rise = RD x 1.7
(RD = distance in feet)
Horizontal distance = HD x 1
(HD = distance in feet)
REMOTE CONDENSER LOCATION
Max. 16.4’ (5 m)
Remote condenser located
ABOVE ice machine
Remote condenser located
BELOW ice machine
HD
RD
DD
Max. 35’ (11 m)
Содержание spika
Страница 60: ...COD 6487_27 04 2017 ...