18
Integrated Technical Vision Ltd
http://www.itvsystems.com.ua
Setting id and IP Address
All panels in RS-485 drop line are connected consecutively. They should have
unique number (id) for their joint operation. It is also necessary that you should set
IP address and subnet mask for local net operation. Address, subnet and 'id'
settings for RS485 drop line are executed using PC connected to the first port (DB9
jack) with null-modem cable.
Switch off the power, set JP3 jumper, connect null-modem cable to DB9 jack (see
Diagram 2).
Switch on the power of the panel, within 40 seconds the panel switches to the
main mode. In process of launching LED4 blinks and then switches off. Now start
ggipcfg.exe program.
Choose 'Action' > 'Search hardware' menu items and press
button. Search of
devices will be executed on all COM ports. In the bottom part of program window
the result of search will be displayed.
Data exchange between PC and NDC-B052 during search will be seen on blinking
of LED4.
If the controller (controllers) are not found out by the program, repeat search.
Observe that during search LED3 is not blinking.
When a control panel (panels) is found select the necessary COM port and
controllers ID in 'Hardware' panel. In 'Configuration parameters' the current configu-
ration of the control panel is displayed.
Setting id and IP Address
Содержание NDC-B052
Страница 1: ...NDC B052 Access Control Panel Installation Manual NDC B052 A C C E S S C O N T R O L P A N E L ...
Страница 2: ...2 Integrated Technical Vision Ltd http www itvsystems com ua ...
Страница 4: ...4 Integrated Technical Vision Ltd http www itvsystems com ua ...
Страница 6: ...6 Integrated Technical Vision Ltd http www itvsystems com ua ...
Страница 23: ...http www itvsystems com ua Integrated Technical Vision Ltd 23 ...