REMOTE MR 400 INSTALLATION
STEP 5: ONLY FOR GREATER DISTANCES THAN 5 METERS BETWEEN UNITS
If the distance between the remote condenser and the split is greater than 5 meters, it
is necessary to add some refrigerant. Add 40 grams per extra meter, up to 15 meters
maximum.
STEP 6: START UP
Now the split unit can be turn on to try it, and modified the control parameters if need
it (electronic board). Instruccions in the user manual.
NOTE: It is better to use the ambient probe from the split unit to obtain the temperature of
the air getting inside the remote condenser (in the air intake of the condenser). To do so,
enlarge the probe cable and put the probe in the condenser.