User Troubleshooting Guide
UNDERCOUNTER MODELS:
PROBLEM
PROBABLE CAUSE
SOLUTION
None of the electrical parts work.
The machine is unplugged.
Plug in the machine and verify
shocket power.
Bin thermostat open. Ice
touching bin tube.
Remove ice from the bin.
Bin thermostat open.
No ice touching bin tube.
Adjust thermostat (electric box
under top cover).
All the electrical parts work but not
compressor. (water doesn´t get frozen).
Compresor
switch is in the “WASH”
position (0).
Switch to “ICE” position (1).
No water in tray.
Not incoming water.
Check water supply.
Inlet strain at water valve blocked.
Check an clean.
Bin full and ice touching thermostat tube,
but machine doesn´t stop.
Bin thermostat doesn´t open (only
operates at harvest time).
Adjust thermostat (electric box
under top cover).
Ice slab empty or too thick.
Disadjusted cycle time.
Adjust thermostat (electric box
under top cover).
Difficult to release ice slab at harvest.
Unit bad leveled (tilted to back).
Level; down front.
Not enough harvest time.
Add more pins to cam timer wheels
(as label indications).
Not uniform flow pattern at evaporator.
Dirty or scaled distributor.
Perform descaling procedure. Remove
and clean distributor (pull from two
clips at distributor sides).
Unit run and stops alternatively itself
Safety presostat opens.
Clean air condenser (behind front grid).
F
or further problems call aftersales service.