Page 11 of 22
Technical Manual No. IOT1000P Effective 8/31/2018
REV LEVEL B
3.
Packing Inspection
Both the oil valve and the atomizing packing should be inspected
regularly for leakage. If any leakage is noted the packing should be
adjusted until the leakage has stopped. See Section III.D for instructions.
4.
Pneumatic System Leaks
The pneumatic system (fittings, solenoid, actuator, etc.) should be
inspected regularly for leakage or other damage. Any leakage or damage
must be repaired or replaced immediately.
5.
Body to End Flange Joint Inspection
Body end flange joints should be inspected regularly for leakage. Any
leakage should be repaired immediately. See following Section for
instructions.
CAUTION
Failure to repair atomizing end flange joint on steam
atomized systems may result in steam cutting of valve
body, end flange assembly or both. This may result in
serious damage to the valve.
B.
Disassembly
All T1000 series Skotch Trifecta Valve Systems may be disassembled without
removal from piping. It is recommended the work area be as clean as possible.
Ensure all manual isolation valves are closed and tagged out, all electrical circuits
are de-energized and isolate the pneumatic supply. BE SAFE!