shut-off 

valve

Recirc Pump

shut-off valve

Air Vent

HOT WA

TER HE

ATE

R

hot 

supply 

line

cold

supply

line

check valve

hose bib

cold 

supply 

line

BS Models

A.  Return into Cold Water Line at Top of Water  

     Heater fig. 3

B.  Return to Drain Valve at Bottom of Water  

     Heater fig. 4

Figures 1,2,3,and 4 are for single line returns only. For multiple branched supply line installations, a recirculation line 

should be installed for each branch.

Note: The Air Vent and Hose Bib are optional with BU models. These models have a built-in air purge valve.

Note: The pump must always be installed below the water level of water heater so that the pump flow is 

always upward or directly horizontal and not downward. Do not mount the pump above the water heater.

3. Wiring Instructions

 

A. Remove the screw at the rear of the motor housing.  Remove the wiring compartment cover.

 

B. Attach the appropriate size electrical connector to the hole in the side of the motor housing.

 

C. Using a minimum size of 14 AWG copper electrical wire (refer to your local code for wiring restrictions),    

 

wire the motor to a single phase power source that matches the electrical rating on the pump nameplate.     

 

See fig. 5.  Use the size of electrical wire as dictated by code.

 

D. Connect a green ground wire at least the size of the power conductors to the ground terminal.

 

E. Electrical supply and ground wires must be suitable for at least 221

º

F (105

º

C).

 

F. Laing circulators are thermally protected and do not require external overload protection.

 

G. If a remote device such as a thermostat/aquastat is connected to the pump it must be wired in series with  

 

 

the power conductor.

4.  Purchase materials required

• Laing e

3

 ReCirc 

 

 

 

• (1)1/2”(5/8”) or 3/4” swing check valve 

• Copper pipe or tubing 

 

 

 

(not required on BU models)

• Tee for under sink connect 

 

 

 

• (1)1/2”(5/8”) or 3/4” hose bib/connection

• Tee or “Y” fitting connection to water heater   

 

(not required on BU models)

• (2) 1/2” (5/8”) or 3/4” shut-off valves   

 

 

• (1)Auto air vent (not required on BU models)

 (not required on BU models) 

 

 

 

• Misc. nipples and fittings 

 

 

 

 

• Pipe insulation

5. Shut off the water to the house.

6. Drain the plumbing lines by opening the faucet/tap in the house.

Drain the water heater if you plan to make the connection at the bottom of the water heater, which requires removal 

of the drain valve. 

7. Connect the return line at the last faucet/taps riser and run to the water heater.

Tee the return line as close to the end of the hot water supply line as possible and run the return line back to the water 

heater.

WARNING: - Electrical Shock Hazard - 

 Disconnect and lock out the power before making electrical 

connections. Failure to follow these instructions could result in serious personal injury or death.

WARNING: - Electrical Shock Hazard - 

 Be 

certain that all connections are secure and the 

conduit box cover is closed before electrical 

power is connected. Failure to follow these 

instructions could result in serious personal 

injury, death and/or property damage.

fig. 5

Содержание Laing Thermotech E1 Series

Страница 1: ...ump The pump only has to produce continuous flow at a pressure sufficient to overcome the friction losses created by the piping in the house water supply line and the return line Oversized Pumps Pumps should not be so large as to produce flow rates that may eventually erode holes in the pipes According to the Copper Development Association excessive erosion occurs at a velocity of about 5ft 1 5m p...

Страница 2: ...han 10º F 6º C below the Set Point The adjustable thermostat is only available on fixed speed motors 2 Plan your installation Decide on the course of the recirculation pipe also determining the length of the pipe required and whether the return line should be connected to the water heater cold water inlet line tee fitting required or to the bottom water heater drain valve Y type fitting required t...

Страница 3: ...ble for at least 221ºF 105ºC F Laing circulators are thermally protected and do not require external overload protection G If a remote device such as a thermostat aquastat is connected to the pump it must be wired in series with the power conductor 4 Purchase materials required Laing e3 ReCirc 1 1 2 5 8 or 3 4 swing check valve Copper pipe or tubing not required on BU models Tee for under sink con...

Страница 4: ...mp pumping away from the water heater nor pumping downward Start the pump before the system is full of water and purged of air Allow the water heater temperature above 140ºF 60ºC only in the US Install the pump in the supply line to faucet taps Use any pipe size other than 1 2 5 8 for all models Position the pump at the top of the water heater Correct Installation Improper Installation Do NOT moun...

Страница 5: ...ng causing the rotor to wobble during operation If the return line connects to the cold water supply at the top of water heater the warm water may be creating back pressure in the cold supply line If so add a check valve non return valve on the cold supply line above the return line tee connector Pump Operating Intermittently or Not at All No power to the pump There is debris or foreign matter in ...

Страница 6: ...the motor leads before continuing Failure to follow these instructions could result in serious personal injury death and or property damage WARNING High Pressure Hazard Pressure may be present in the pump body This pressure can be relieved by loosening the flange bolts and shifting the pump assembly slightly to allow the pressurized water to escape Failure to follow these instructions could result...

Отзывы: