WIRING DIAGRAMS

For Motorized Valves, refer to the valve manufacturer's wiring instructions.

Pump Control Only

1. Install a starter or relay in pump control circuit, 

as shown, to prevent damage to snap switch 
and help insure proper switch/control operation.
Failure to do so may shorten the life of the switch
when actual amperage exceeds switch rating.

2. Connect wires from holding coil of pump starter 

or relay to terminals 1 and 2 as shown.

1. Main Line Switch - For burner circuits within 

the switch’s electrical rating.

2. Pilot Switch  - To holding coil of a starter when 

the burner circuit exceeds the switch’s electrical 
rating.

1 2

4 5 6

ALARM

NEUTRAL

HOT

ALARM

NEUTRAL

HOT

1 2

4 5 6

1 2

4 5 6

SEE PUMP

CONTROL

CIRCUIT

TO NEUTRAL

TO BURNER CONTROL CIRCUIT   

HOT

ALARM

1 2

4 5 6

LOAD

LINE (3 PHASE)

SEE PUMP

CONTROL

CIRCUIT

ALARM

1 2

4 5 6

LOAD

LINE

OR

OR

Combination Pump Control, Low Water Cut-Off and Alarm

Alarm Circuit Only

1. Low Water Alarm

2. High Water Alarm

NOTE

To help insure most effective operation,
balance boiler feed pump(s) to deliver
required water feed rate to match boiler
steaming requirements.

NOTE

For Model 159S, use terminals 5 and 6 from
starter or relay for pump #2.

Low Water Cut-Off Only

1. Main Line Switch - For burner circuits within the 

switch’s electrical rating.

LINE

LOAD

1 2

4 5 6

1 2

4 5 6

LOAD

LINE

OR

2. Pilot Switch - To holding coil of a starter when 

the burner circuit exceeds the switch’s electrical
rating.

Содержание 150S-HD

Страница 1: ...off must be installed in series with all other limit and operating controls installed on the boiler After installation check for proper operation of all of the limit and operating controls before leav...

Страница 2: ...FFERENTIAL 19mm PUMP OFF PUMP ON 3 4 DIFFERENTIAL 19mm PUMP OFF BURNER OFF NORMAL BOILER WATER LINE 113 16 DIFFERENTIAL 46mm OPERATION Maximum Pressure 150 psi 10 5 kg cm2 Electrical Ratings Settings...

Страница 3: ...ening or closing will occur at slightly different levels than indicated above Model 158S 150 psi 10 5 kg cm2 Levels 0 psi 0 kg cm2 150 psi 10 5 kg cm2 Pressure Settings and Differential Pressures cont...

Страница 4: ...8 DIFFERENTIAL 35mm Values are 8 3 2mm 150 psi 10 5 kg cm2 Levels Approximate Distance Above Cast Line Differential Setting In mm In mm Pump 1 Off 15 16 24 5 16 8 Pump 1 On 5 8 16 Pump 2 Off 5 8 16 3...

Страница 5: ...boiler to a level which is below the float chamber A Allow the boiler to cool to 80 F 27 C and release the boiler pressure to 0 psi 0 bar b Using a flathead screwdriver remove the junction box cover B...

Страница 6: ...ew head gasket J on the sealing surface of the control body a Carefully remove the new replacement head mechanism from the carton Handle it carefully to prevent damage to the float rod G K D c Install...

Страница 7: ...lay is used in conjunction with it To prevent electrical shock turn off the electrical power before making electrical connections This low water cut off must be installed in series with all other limi...

Страница 8: ...larm off Boiler feed pump on burner off alarm on 1 2 4 5 6 1 2 4 5 6 1 2 4 5 6 Motorized valve closed burner on alarm off Motorized valve open burner on alarm off Motorized valve open burner off alarm...

Страница 9: ...al rating 1 2 4 5 6 ALARM NEUTRAL HOT ALARM NEUTRAL HOT 1 2 4 5 6 1 2 4 5 6 SEE PUMP CONTROL CIRCUIT TO NEUTRAL TO BURNER CONTROL CIRCUIT HOT ALARM 1 2 4 5 6 LOAD LINE 3 PHASE SEE PUMP CONTROL CIRCUIT...

Страница 10: ...erification of proper operating sequence If the burner comes on immediately turn the boiler off and make the necessary corrections Failure to follow this warning could cause an explosion or fire and r...

Страница 11: ...on NOTE Refer to page 2 for switch operating points Open upper valve 1 Slowly open the lower valve 2 Water in the sight glass should lower As the water in the sight glass lowers the pump should turn o...

Отзывы: