PS200 Configuration & Operation Guide
APPENDIX A-3 PARAMETER LISTING
Page 128
Speed C
ontr
ol
Single Pum
p
Multi-pum
p
Group 17
ANALOG INPUTS
Description
MAXIMUM AI2
Defines the maximum value for analog input AI2.
20 MA
[default]
Maximum scaled setting is at 20 MA
TUNED VALUE
Select tuned value after the tune function has been completed. This will select the
tuned value for the maximum value of AI2.
X
X
X
17.11**
TUNE
This parameter sets the maximum value of the signal to be applied to AI2. When
TUNE is selected and ENTER is pressed the tuned value for AI2 is set to the actual
AI2 value when the tune function was activated. This function is useful for
zeroing out any system hysteresis.
X
X
X
17.12**
SCALE AI2
Scales AI2. Default = 100%
X
X
X
17.13**
FILTER AI2
Defines the filter time constant for AI2. Default is 0.1 sec. Note the signal is also
filtered due to the signal interface hardware (10ms time constant). This cannot be
changed by any parameter.
INVERT AI2
Activates/deactivates the inversion of analog input signal AI2.
NO
No inversion
X
X
X
17.14**
YES
Inversion is active. The maximum value of the analog input signal (20 mA)
corresponds to 16.04 AI2 MIN and the minimum value of the analog input signal
(4mA) corresponds to 16.03 AI2 MAX
MINIMUM AI3
Defines the value for analog input AI3.
0 MA
Do not use. A 0-mA signal will activate a Sensor Failure fault function unless
24.01 and 24.02 are disabled.
4 MA
[default]
4 mA is selected as the minimum value.
TUNED VALUE
Select tuned value after the tune function has been completed. This will select the
tuned value for the minimum value of AI3.
X
X
X
17.15
TUNE
This parameter sets the minimum value of the signal to be applied to AI3. When
tune is selected and enter is pressed the tuned value for AI3 is set to the actual
AI3 value when the tune function was activated. This function is useful for
zeroing out any system hysteresis.
MAXIMUM AI3
Defines the maximum value for analog input AI3.
20 MA
[default]
Maximum scaled setting is at 20 MA
TUNED VALUE
Select tuned value after the tune function has been completed. This will select the
tuned value for the maximum value of AI3.
X
X
X
17.16**
TUNE
This parameter sets the maximum value of the signal to be applied to AI3. When
TUNE is selected and ENTER is pressed the tuned value for AI3 is set to the actual
AI3 value when the tune function was activated. This function is useful for
zeroing out any system hysteresis.
X
X
X
17.17**
SCALE AI3
Scales AI3. Default = 100%
X
X
X
17.18**
FILTER AI3
Defines the filter time constant for AI3. Default is 0.1 sec. Note the signal is also
filtered due to the signal interface hardware (10ms time constant). This cannot be
changed by any parameter.
INVERT AI3
Activates/deactivates the inversion of analog input signal AI3.
NO
No inversion
X
X
X
17.19**
YES
Inversion is active. The maximum value of the analog input signal (20 mA)
corresponds to 16.09 AI2 MIN and the minimum value of the analog input signal
(4mA) corresponds to 16.08 AI2 MAX
AI1 CONFIG
Defines the configuration for AI1
PROC TRANS 2
Used with offset feature.
EXT SETPOINT
Used when fixed or variable setpoint is sent via an external source in single pump
or multi-pump.
VIBRATION 2
Used when Vibration 2 is selected
CONDITION 2
Used when Condition 2 is selected
SPD CTRL REF
Used in Speed Macro when an external speed Setpoint is present.
PWM SIGNAL
Used when the Pump Wear Monitor is selected.
X
X
X
17.20
NOT USED
[default]
AI1 not used
AI2 CONFIG
Defines the configuration for AI2
PROC TRANS 1
Default setting for single pump and multi-pump
SPD CTRL REF
Used in Speed Macro when an external speed Setpoint is present.
X
X
X
17.21
NOT USED
AI2 not used (Default for Speed Macro)
AI3 CONFIG
Defines the configuration for AI3 (MUST BE A LINEAR SIGNAL).
VIBRATION 1
Used when Vibration 1 is selected
CONDITION 1
Used when Condition 1 is selected
PWM SIGNAL
Used when the Pump Wear Monitor is selected.
PROC TRANS 2
Used with offset feature.
EXT SETPOINT
Used when fixed or variable setpoint is sent via an external source in single pump
or multi-pump.
X
X
X
17.22
NOT USED
[default]
AI3 not used
Содержание PumpSmart PS200
Страница 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 26: ......
Страница 72: ......
Страница 105: ......
Страница 119: ......
Страница 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Страница 147: ......
Страница 158: ......