Under-Compensated system
: In this case, the drive is under-compensating to the error in the setpoint. The
integration time in this case is too long.
DERIVATIVE RESPONSE
NOTE - The Derivative function can be found in the Advanced Parameter section accessible by the 564 User Pass
Code.
Derivative action completes the PID controller capability and is useful in systems where there is a sudden change in
process variable. Derivative action will respond to a sudden change in process variable with a response similar to a
high proportional gain but after this initial response behaves similar to a PI controller. Derivative action will
respond to a sudden change in process variable faster then by just using PI control. In most pump applications PI
control will be sufficient. However, PID control may be very useful in some level and temperature control
applications.
Parameter
Name
Value/Range
Notes
13.05
D - TIME
0-10 sec
0 [default]
Defines the derivation time of the PID
controller.
13.06
PID DERIV FILTER
0.4-10 sec
1 [default]
Defines the time constant of the filter
used to smooth the derivative
component of the process PID controller
Содержание PumpSmart PS200
Страница 1: ... PUMPSMART CONTROL SOLUTIONS PS200 Version 4 0 Configuration Operation Guide ...
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 26: ......
Страница 72: ......
Страница 105: ......
Страница 119: ......
Страница 146: ...PS200 Configuration Operation Guide APPENDIX A 3 PARAMETER LISTING Page 143 ...
Страница 147: ......
Страница 158: ......