ELECTRICAL CONNECTIONS

Remember that the starting current in direct on-line
starting can be up to six times higher than the rated
current. Make sure that the fuses or circuit breakers
are of the proper rating.

The Data plate gives rated current. Fuse rating and
cable shall be selected in accordance with local rules
and regulations. Note that with long cables, the
voltage drop in the cable must be taken into consider-
ation, since the motor’s rated voltage is the voltage
that is measured at the terminal board in the pump.

The overload protection (motor protection breaker) for
direct on-line starting shall be set to the motor rated
current as given on the data plate.

Check the phase sequence in the mains with the
phase sequence indicator.

If intermittent operation is prescribed (see Data Plate),
the pump shall be provided with control equipment
that provides such operation.

Single phase operation

The Flygt single phase pumps must be equipped with
a starter which has start and run capacitors.

A special Flygt designed starter is required for the
operation of single phase 3067 pumps. The connec-
tion of the motor cable to the starter is shown in the
wiring diagram.

NOTE! It is not possible to change the direction of
rotation of a single phase pump by changing the cable
conductors on the starter. Please contact your nearest
Flygt representative.

Monitoring equipment

The

 FLS

 sensor consists of a small float switch for

sensing water in the stator housing. Its design makes
it suitable for pumps in vertical installations.

The FLS sensor is installed in the bottom of the stator
housing.

The sensor is not applicable to Ex-approved pumps.

Check:

— signals and tripping function.

— that relays, lamps, fuses and connections are

intact.

Replace defective equipment.

Содержание Flygt 3067

Страница 1: ...Installation Care and Maintenance 3067 892397 08 ...

Страница 2: ...s well as those responsible for operation or maintenance The operating instruc tions should always be readily available at the location of the unit WARNING Qualificationsofpersonnel An authorized certified electrician and mechanic shall carry out all work Safetyregulationsfortheowner operator All government regulations local health and safety codes shall be complied with All dangers due to electri...

Страница 3: ...mber O ATEX marking D A N K L M C B F E G I J H O EN EuropeanNorm ATEX Directive EN 50014 EN 50018 EN 1127 1 II 2 G EEx dII T4 3067 090 3067 590 3067 890 I M 2 EEx dI 3067 690 Generaldataplate A Serial number B Product code Number C Curve code Propeller code D Country of origin E Product number F Additional information G Phase Type of current Frequency H Rated voltage I Thermal protection J Therma...

Страница 4: ...act your Flygt representative PRODUCT DESCRIPTION Introduction Thank you for buying a submersible Flygt pump In this Installation Care and Maintenance manual you will find general information on how to install and service the 3067 pump to give it a long and reliable life Application This Installation Care and Maintenance manual applies to a submersible Flygt pump If you have bought an Ex approved ...

Страница 5: ...ase induction motor for 50 Hz or 60 Hz The motor can be started by direct on line or star delta starting The motor can be run continuously or intermittently with a maximum of 15 evenly spaced starts per hour Flygt motors are tested in accordance with IEC 34 1 The stator is insulated in accordance with class F 155 C 310 F The motor is designed to deliver its rated output at 5 variation from the rat...

Страница 6: ...the sump before the pump is lowered down and the station is started Special rules apply to installation in explosiveatmosphere Intrinsically safe circuits are normally required Ex i for the automatic level control system by levelregulators Minimum stop level should be according to the dimensional drawing The pump must never run dry Safety precautions In order to minimize the risk of accidents in c...

Страница 7: ...ng to the approval of the product All electrical work shall be carried out under the super vision of an authorized electrician Local codes and regulations shall be complied with Check on the data plate which voltage supply is valid for your pump Check that the main voltage and frequency agree with the specifications on the pump data plate If the pump can be connected to different voltages the conn...

Страница 8: ...ribed see Data Plate the pump shall be provided with control equipment that provides such operation Single phase operation The Flygt single phase pumps must be equipped with a starter which has start and run capacitors A special Flygt designed starter is required for the operation of single phase 3067 pumps The connec tion of the motor cable to the starter is shown in the wiring diagram NOTE It is...

Страница 9: ...T1 blue T2 Stator leads V2 blue W2 black U2 green U1 red V1 brown W1 yellow 7GX 3 phase direct on line Conductors Connection starter SUBCAB7Gx 1 black L1 2 black L2 3 black L3 4 black L1 5 black L2 6 black L3 yellow green earth SUBCAB7Gx 2x1 5 1 black L1 2 black L2 3 black L3 4 black L1 5 black L2 6 black L3 T1 black T1 T2 black T2 yellow green earth Terminalforconnectionofthermalcontactsinthemoto...

Страница 10: ...registered trademark of ITT Flygt AB for electrical cables Stator leads V2 blue W2 black U2 green U1 red V1 brown W1 yellow Single phase Conductors Connection starter SUBCAB 4Gx 1brown red 1 SUBCAB xAWG 4 2 black black 2 HØ7RN F 4Gx 3 blue white 3 BIHF 4Gx silicon yellow green earth SUBCAB 4Gx 2x1 5 1 brown 1 2 black 2 3 blue 3 yellow green earth T1 black T1 T2 black T2 SUBCAB 7Gx 1 black 1 2 blac...

Страница 11: ...of burn injuries Starting jerk Watch out for the starting jerk which can be powerful The pump can be transported and stored in a vertical or horizontal position Always lift the pump by its lifting handle never by the motor cable or the hose Make sure that the pump cannot roll or fall over and injure people or damage property The pump is frostproof as long as it is operating or is immersed in the l...

Страница 12: ...azardous chemicals have splashed into your eyes Rinse your eyes immediately in running water for 15 minutes Hold your eyelids apart with your fingers Contact an eye specialist On your skin Remove contaminated clothes Wash your skin with soap and water Seek medical attention if required Inspection Regular inspection and preventive maintenance ensure more reliable operation The pump should be inspec...

Страница 13: ...k after changing the oil The oil housing may be under pressure Hold a rag over the oil plug to prevent splatter 1 Lay the pump on its side on a bench or over two supports Unscrew the oil housing screw oil plug and drain the oil 2 Fill with oil A paraffin oil with viscosity close to ISO VG15 is recommended e g Mobil Whiterex 309 The pump is delivered from factory with this type of oil In applicatio...

Страница 14: ...roduct code 3 3067 090 180 250 590 690 170 890 50 Hz 1 2 kW 2840 rpm 60 Hz 1 4 kW 3400 rpm 50 Hz 1 2 kW 1350 rpm 60 Hz 1 3 kW 1650 rpm 1 50 Hz 0 9 kW 2800 rpm 50 Hz 1 0 kW 2840 rpm 60 Hz 1 2 kW 3450 rpm 50 Hz 0 8 kW 1400 rpm 60 Hz 1 0 kW 1700 rpm ...

Страница 15: ...15 HYDRAULIC ENDS C M B F ...

Страница 16: ...16 HYDRAULIC ENDS D D D ...

Страница 17: ...17 DIMENSIONS AND WEIGHTS C 3067 090 180 All dimensions in mm in ...

Страница 18: ...18 DIMENSIONS AND WEIGHTS D 3067 090 180 All dimensions in mm in ...

Страница 19: ...19 DIMENSIONS AND WEIGHTS B D 3067 250 590 690 All dimensions in mm in ...

Страница 20: ...20 DIMENSIONS AND WEIGHTS M 3067 170 890 All dimensions in mm in ...

Страница 21: ...21 DIMENSIONS AND WEIGHTS MH All dimensions in mm in FP 3067 090 180 All dimensions in mm in ...

Страница 22: ...22 Most recent Pump No Hours of Remarks Sign service date operation SERVICE LOG ...

Страница 23: ......

Страница 24: ...www flygt com 3067 01 08 Eng 2M 06 02 ITT FLYGT AB Printed in Sweden 892397 ...

Отзывы: