8
RED
BLACK
BLUE
WHITE
RED
BLACK
BLUE
WHITE
DN65 - qp 25
DN80 - qp 40
DN100 - qp 60
DN150 - qp 150
Pulse Weight
Pulse Length (ms)
8
p/L
5
n.a.
n.a.
n.a.
4
p/L
n.a.
5
n.a.
n.a.
2
p/L
n.a.
n.a.
5
5
1
L/p
20
20
10
10
2,5
L/p
50
50
20
50
10
L/p
100** (200, 500)
100** (200)
100
100
25-2500
L/p
100** (200, 500)
100** (200, 500)
100** (200, 500)
100** (200, 500)
**standard: 100ms, values in brackets only if specified in model options table
Always make sure that the housing and gasket line up properly.
4.2 - Specification of connection to integrator
Cable A: 4 wires connecting cable, used for connection to integrator
Allocation of wire colors:
1 - WHITE: µCom/diagnostic
2 - BLUE: pulse A or diagnostic
3 - BLACK: earth connection (-)
4 - RED: power supply AXONIC (+)
Cable B: 3 wires connecting cable, used for connection to any devices
Allocation of wire colors:
• RED: Pulse B
• BLACK: earth connection (-)
• WHITE: DIR. (Direction of the flow: 1 = normal flow, 0 = backword flow)
4.3 - Characteristic of pulse outputs (A+B):
• conform to class OB, OC and OD of EN1434-2
• Type:
Open Drain
• Polarity:
non reversible (observe connection diagram)
• Duration of pulse:
see table below
• Max voltage:
30V DC
• Max current:
27 mA
• Drop of voltage when switched on:
≤ 0.3V at 0.1 mA /≤ 2V at 27 mA
• Max output frequency:
128 Hz
• Resistance when switched off:
≥ 6MΩ
• Pulse length according table
• Max. cable length:
10 m
Connection AXONIC/CF51-CF55-Pulse-Box
Connection AXONIC/C800