Chapter 3 Connecting the 60WP
30
Water Solutions 60WP Endpoint Installation Guide
1.
Remove the protective cover from the end of the cable.
Figure 10: 60WP Endpoint With 5-Foot Cable
2.
Connect each cable wire to the appropriate meter register screw terminal as indicated
in the table below.
60WP Cable Wire Color
Elster/AMCO Digital Register Screw Terminal
Red B
White G
Black R
Using an Extended Cable
If you need to extend the length of the existing endpoint cable (up to a maximum of 300
feet), additional cable can be ordered from Itron.
For cable lengths exceeding 150 feet, you must update the endpoint's operating parameters.
This is accomplished by reprogramming the endpoint and selecting the appropriate cable
length description during the programming operation. Failure to update the parameters
could affect the endpoint's ability to count accurately.
For more information, see
Programming the 60WP Endpoint
on page 32.