APT3100
Smart Pressure Transmitter
Operation Manual M3100-EO1G
38
Duon System Co.,Ltd.
5.4 Check Output
Before other handle transmitter to on-line, you must examine and confirm whether transmitter
currently operate and suitably configure progress variable.
5.4.1 Process Variable
We use two progress variable in APT-3100 SMART Pressure Transmitter pressure value is Primary
Variable and temperature value of pressure value configure SV(Secondary Variable) with fixed
value.
Moreover this PV value ouputs with 4~20mA analog value.
5.5 Basic Setup
You must configure correlation variable for operating currently transmitter.
5.5.1 Select Sensor Range
Pressure range to measure is depended Range Code of sensor. This value is classified from
pressure sensor module automatically.
5.5.2 Set Output Units
Select from the following engineering units:
Unit: kPa, kg/cm2, bar, psi, mmH2O etc
5.5.3 Rerange
Set the Zero and Span of 4~20mA analog output.
5.6 Detailed Setup
5.6.1 Set Fail Mode
When sensor is wrong or microprocessor of transmitter doesn't operate normally in order to
outputs current value of High or Low.
5.6.2 Set Damping Time
The sensor input value changes the response time of the transmitter to smooth variations in output
readings caused by rapid changes in input. Determine the appropriate damping setting based on
the necessary response time, signal stability, and other requirements of the loop dynamics of your
system. The default damping value is 1.0 seconds, and can be reset to damping values between 0
and 60 seconds.
www.
.com
1.800.561.8187