5.3. User settings
Note
The settings mode for the configuration settings as
well as for the user settings become available only
after the sensor has been paired with the ventilation
unit.
Modify and confirm one of the settings below and
then repeat the procedure for each desired setting.
Tip
If more than one sensor is in use, you need only to
configure the settings for one sensor (of the same
type). The other sensors (of the same type) will
automatically be set to the same settings.
To enter the settings mode for the user settings menu,
you must first switch off power to the sensor and then
restore power to the sensor You then need to wait for
2
minutes
. After
2 minutes
press and hold the touch button
until the status LED lights up blue.
Then push and hold the touch button for a minimum of 5
seconds, after which you can release it after:
If the status LED is blinking orange:
●
5 to 7 seconds: Sending a reset message for the dirty
filter indication. A reset message is sent to the
ventilation unit.
Note
If you select reset dirty filter, your choice will be
implemented immediately and the menu will
automatically close.
After a successful dirty filter reset, the status LED will
flash green in confirmation.
●
7 to 9 seconds: User setting 1: Sensitivity to rising
humidity. Press and hold the touch button until the
status LED is lit blue and the timer flashes. Briefly
press the touch button:
-
Option 1: Rise of 3% in 24 seconds (default).
-
Option 2: Rise of 3% in 48 seconds.
Confirm your choice by pressing and holding the touch
button for 5 seconds until the status LED flashes blue.
The selected setting can be modified according to the
schemes below.
Always press the touch button to go to the next option.
22