Technical data
Unit Electrical Data
(*) The dimensioning of the unit’s power cables is the responsibility of the installer, who shall consider: the rating, the maximum
working temperature in the room, the type of insulation and the cable laying, the maximum length of the power supply line.
VLH HE
504
554
604
704
804
904
1004
Rated voltage
V-ph-Hz
400 (±10%)/3/50
Max. absorbed power
kW
60,8
68,8
73,4
90,2
100,6
112,3
124
Rated current
A
88,3
96,7
105,3
127,4
141,6
155,8
170
Max. current FLA
A
104,5
114,5
124,9
151,4
168,8
186,8
204,8
Max. start-up current LRA
A
246
260
271
328
392
410
428
External fuses
(A)
160
160
160
200
200
250
250
Max. cable section(*)
mm
2
70
70
70
3x95
3x95
3x120
3x120
Exchanger Resistance
Power supply
V(%)-ph-Hz
230 (±10%)/1/50
Max. absorbed power
kW
130
VLH
504 554 604 704 804 904 1004
1104
1204
Number
4
4
4
4
4
4
4
4
4
Nominal power input
kW
(9+13,7)
(12+13,7) (13,7+13,7) (13,7+18,6) (13,7+23,0) (13,7+23,0) (23,0+23,0) (25,3+25,3) (25,3+25,3)
x 2
x 2
x 2
x 2
x 2
+(23,0+23,0)
x 2
+(20,3+20,3)
x 2
Max. absorbed power
kW
(11+17,3)
(15+17,3) (17,3+17,3) (17,3+23,8) (17,3+29)
(17,3+29)
(29+29)
(35,2+35,2) (35,2+35,2)
x 2
x 2
x2
x 2
x 2
+(29+29)
x 2
+(28,1+28,1)
x 2
Rated current
A
(15,8+24,3) (20+24,3) (24,3+24,3) (24,3+31,4) (24,3+38,5) (24,3+38,5) (38,5+38,5) (44,2+44,2) (44,2+44,2)
x 2
x 2
x 2
x 2
x 2
+(38,5+38,5)
x 2
+(34,3+34,3)
x 2
Max. current
A
(19+29,2)
(24+29,2) (29,2+29,2) (29,2+38,5) (29,2+47,2) (29,2+47,2) (47,2+47,2)
(62+62)
(62+62)
x 2
x 2
x 2
x 2
x 2
+(47,2+47,2)
x 2
+(47,5+47,5)
x 2
Oil pan resistor
W
(65-75)
(65-75)
(75-75)
(75-130)
(75-130)
(75-130-
(130-130)
(150-150)
(150-150)
x 2
x 2
x 2
x 2
x 2
130-130)
x 2
x 2
x 2
Compressors Electrical Data
Manuale VLS-VLH2 17-06-2005 11:17 Pagina 47