Technical data
Unit Electrical Data
VLH
STD
504 554 604 704 804 904 1004
1104
1204
Rated voltage
V-ph-Hz
400 (±10%)/3/50
Max. absorbed power
kW
59,4
67,4
72
88,2
104,6
110,3
112,3
135
149
Rated current
A
85,6
94
102,6
123,4
137,6
155,8
170
N.D.
N.D.
Max. current FLA
A
101,8
111,8
122,2
147,4
164,8
186,8
204,8
235
264
Max. start-up current LRA
A
248
258
268
324
388
392
428
493
522
External fuses
(A)
160
160
160
200
200
200
200
250
315
Max. cable section(*)
mm
2
70
70
70
3x95
3x95
3x120
3x120
3x185
3x185
Exchanger Resistance
Power supply
V(%)-ph-Hz
230 (±10%)/1/50
Max. absorbed power
kW
130
(*) The dimensioning of the unit’s power cables is the responsibility of the installer, who shall consider: the rating, the maximum
working temperature in the room, the type of insulation and the cable laying, the maximum length of the power supply line.
N.D. Not available.
VLH
LN
504 554 604 704 804 904 1004
1104
1204
Rated voltage
V-ph-Hz
400 (±10%)/3/50
Max. absorbed power
kW
58,5
66,5
72,0
86,0
96,4
109,3
121,0
132
146
Rated current
A
83,6
92
102,3
118,4
132,5
149
163,2
N.D.
N.D.
Max. current FLA
A
99,8
109,8
121,9
142,3
159,7
180
198
228
257
Max. start-up current LRA
A
246
256
268
317
383
403
421
486
515
External fuses
(A)
160
160
160
200
200
250
250
250
315
Max. cable section(*)
mm
2
70
70
70
3x95
3x95
3x120
3x120
3x185
3x185
Exchanger Resistance
Power supply
V(%)-ph-Hz
230 (±10%)/1/50
Max. absorbed power
kW
130
VLH
ELN
604 704 804 904 1004
1104
1204
Rated voltage
V-ph-Hz
400 (±10%)/3/50
Max. absorbed power
kW
72,0
87,2
97,6
109,3
121,0
132
146
Rated current
A
102,3
120,6
134,8
149,0
163,2
N.D.
N.D.
Max. current FLA
A
121,9
144,6
162
180
198
228
257
Max. start-up current LRA
A
267,7
321,1
384,8
402,8
420,8
486
515
External fuses
(A)
160
200
200
250
250
250
315
Max. cable section(*)
mm
2
70
3x95
3x95
3x120
3x120
3x185
3x185
Exchanger Resistance
Power supply
V(%)-ph-Hz
230 (±10%)/1/50
Max. absorbed power
kW
130