Configuration

pH

7.60

   SP

7.00

   Out 1   021%

   Out 2   070%

m3h     10.

5

CONFIG                           21.3ºC

pH

7.60

   SP

7.00

   Out 1   021%

   Out 2   070%

m3h     10.

5

CONFIG                           21.3ºC

PH

m3h

10.5

7.6

0

1

0

1

ACID

ALK.

PH

m3h

10.5

7.6

0

1

0

1

ACID

ALK.

4. OPERATION

4.1 Main screen and navigation

Confirm
Exit without 

confirming
Increase / decrease value, 

and move up /down

Move left / right

ENT

ENT

ESC

Regulating 

output 1

Move the cursor to select the following menu: 

pH, m3h or CONFIG, and enter with ENTER

Warnings on the main screen:

Flashing reading: pH alarm

Flashing regulation output: no device detected on the 4-20 mA output

Flashing regulation outputs (both): remote control deactivated, or no 

device connected to the 4-20 mA outputs

Press ENTER to edit the setpoint 

or move the cursor to enter the 

following menu:

CAL: Calibration

CONTROL: control output

ALARM: alarms

REGISTER: output for register

pH regulation 

output

Flow rate reading

Access to the Configuration menu

Calibration menu

Alarm menu

Control menu

Register menu

Cursor

Regulating 

output 2

pH

CAL

CONTROL

ALARM

REGISTER

SP

07.00

PH CAL.

Point 1

      07.00

Point 2        04.00

Reading      07.23

PH CONTROL

CONTROL

PI CONTROL

PH ALARM

Rearm:

 Yes; No

Stop: pH;

 All; None

pH +

 1.00

            025 

s

pH -

 0.50

            060 

s

PH REGISTER

Out:

       4-20 mA

 2

  4 mA:

              00.00

20 mA:

              14.00

Содержание WTRTEC RED

Страница 1: ...WTRTEC ENGLISH...

Страница 2: ...4 4 1 Activation of the control 8 4 4 2 Advanced control configuration PIQ control 9 4 5 Alarms 11 4 5 1 pH alarms 11 4 5 2 Zero flow alarm 11 4 5 3 Flow detector alarm 11 4 6 Configuration of the re...

Страница 3: ...oning and maintaining the equipment must follow the instructions in this manual with special attention to the detailed recommendations and warnings The specific instructions for the use of the chemica...

Страница 4: ...or base dosing pumps WTRTEC Red enables monitoring remote management and historical logging by means of a mobile web application A communications Gate Ref 01 006 is needed for this which can be conne...

Страница 5: ...ted Flow meter power supply 12 VDC 100 mA pH sensor 0 00 14 00 Isolated pH EC temperature sensor 0 0 100 C 32 0 212 F PT100 Remote input ON OFF 12 24 V AC DC Flow detector ON OFF NPN isolated Outputs...

Страница 6: ...gulation output no device detected on the 4 20 mA output Flashing regulation outputs both remote control deactivated or no device connected to the 4 20 mA outputs Press ENTER to edit the setpoint or m...

Страница 7: ...buffer value using the up down arrows Insert the sensor into the point 1 buffer wait until the sensor reading is stable and confirm with ENTER Repeat the operation with the point 2 buffer Before putt...

Страница 8: ...ecirculating tank The regulating output establishes 5 minute cycles in PH CONTROL Out 2 4 20 mA 2 Limit out 2 080 Pump 2 1200 l h PH CONTROL OUT 1 OUT 2 PH CONTROL Control ON Out 1 4 20 mA 1 Limit out...

Страница 9: ...ng parameters for this control are in the PI CONTROL menu PH CONTROL CONTROL PI CONTROL ENT PH PI CONTROL PIQ PpH 030 Kp 20 Ki 30 T delay 020 s Q test 00 00 m3h PIQ PpH The PIQ control mode to adjust...

Страница 10: ...mulated error and enables reading stabilisation once the setpoint value has been achieved It is only valid for in line controls For recirculating controls it must be Ki 0 T delay seconds T delay is th...

Страница 11: ...top enables shutting down of the dosing control output for the alarmed control parameter for all or none 4 5 2 Zero flow alarm An alarm can be set to warn that there is no flow in the main pipe If the...

Страница 12: ...ENT 4 6 Configuration of the register outputs If any of the 4 20 mA analogue control outputs is unused these can be used to be configured as outputs for logging any sensor readings To do this the outp...

Страница 13: ...inute ENT CONFIG COMMUNICATIONS Node 02 Baudrate 1200 Parity N Stop bits 1 CONFIG SET UP COMUNICATIONS CHECK MONITOR 4 7 3 Information on the unit and monitor This screen displays information on the e...

Страница 14: ...21 0 5 INSTALLATION A place protected from water away from heat and direct sunlight must be chosen for installation 5 1 Installation diagram In line pH control In tank pH control Device Mixer ACID ACI...

Страница 15: ...event abrupt starts 13 1 4 5 6 7 8 8 9 3 2 9 15 10 11 12 14 110 240 VAC power supply 12 VDC power supply RemoteON OFFinput canbeactivatedwith12 24VAC DC pH alarm output Relay Flow rate alarm output Re...

Страница 16: ...nnect the pumps see Installing and Wiring 2 Equipment calibration and configuration Calibrate the sensors pH flow meter etc see Calibration Configure the equipment Setpoint Type of control Installatio...

Страница 17: ...17 Maintenance 7 MAINTENANCE 45602 45603 45604 45606 40604 44619 45606 45607 45 615 M12 33654...

Страница 18: ...1 pitch black 2 44619 Female angled terminal strip 3 pins 5 pitch 2 40604 Female angled terminal strip 6 pins 5 pitch 1 45605 Female angled terminal strip 3 pins 7 5 pitch 1 45 615 M12 Hose cable M12...

Страница 19: ...nstruction manual Ant n Planas Manager WARRANTY I T C S L guarantees the product specified in this document for a period of 1 year from the date of purchase against all manufacturing or material defec...

Страница 20: ...ginal Manual Ed 6 3 2020 EN C Vall s 26 Pol Ind Can Bernades Subir P O Box 60 08130 Santa Perp tua de Mogoda BARCELONA SPAIN Tel 34 93 5443040 Fax 34 93 5443161 e mail itc itc es www itc dosing pumps...

Отзывы: