                                          6

. RS232 SERIAL PORT COMMUNICATION

11

When the communication distance is less than15M, the two sides can communicate directly 
connected, and just by using the three lines(transmit line, the receiving line, and the signal ground)
can achieve full-duplex a synchronous serial communication.

When there is no Modem, the maximum communication distance is calculated as follows

RS-232C standard says: When the error rate is of 4%, the required wire capacitance value should be 
less than 2500PF. For ordinary Wire, the capacitance value is about 170PF / M. 
Allowed distance L = 2500PF / (170PF / M) = 14.7M. calculating this distance, is a conservative. In the 
practical applications, when using 9600bps and ordinary shielded twisted pair cable, the distance 
can be up to 30 to 35 meters.

The following figure is the easiest way to connect MODEM zero (that is, three-wire connection), And
the 2nd line 3rd line is cross-connect in the figure, because even when direct way to communicate 
both look as data terminal equipment, can also be sent to both parties and received from the other. 
In this way, either party of the communication can start sending and receiving , as long as there is a 
valid request to send RTS efficiently and DTR data terminal is well ready.

Minimalist zero Modem connection of (3-wire)

6.2 Communication protocol  Settings

communication Settings: 8 bits 1 stop bit, no check

                                          

6.1

. NFC(Near Field Communication)

6.2.1 PC protocol format will be issued on a single chip digital amplifier host state:

Start byte

Instruction type byte

Instruction type

Checksum byte

0xAA

0x05

0x01/Abnormal

0x2E/Abnormal

0x02/Normal

0x2D/Normal

0x03/standby power

0x2C/standby power

0x04/no shaking signal

0x2B/no shaking signal

RXD

TXD

GND

TXD

RXD

RTS

T-4D500R

PC

CTS

DSR

SG

DCD

DTR

RI

1

DCD

2

RxD

3

TxD

4

DTR

5

  SG

6

DSR

7

RTS

8

CTS

9

RI

DB-9

RX TX GND

1

2

3

Содержание T-1D120R

Страница 1: ...ION MANUAL PUBLIC ADDRESS SYSTEM CLASS D AMPLIFIER T 1D120R 1D240R 1D350R 1D500R T 2D120R 2D240R 2D350R 2D500R T 4D120R 4D240R 4D350R 4D500R POWER CH1 OFF ON T 1D120R CLASS D AMPLIFIER PROT CLIP SIG S...

Страница 2: ...D240R 2D350R 2D500R 5 3 4 Rear Panel T 2D120R 2D240R 2D350R 2D500R 5 3 5 Front Panel T 4D120R 4D240R 4D350R 4D500R 6 3 6 Rear Panel T 4D120R 4D240R 4D350R 4D500R 6 4 OPERATING INSTRUCTION 7 5 WIRING I...

Страница 3: ...r Make no further attempt to operate the unit in this condition as this may cause fire or electric shock If you detect smoke or a strange smell coming from the unit If water or any metallic object get...

Страница 4: ...ects on the unit as this may cause it to fall or break which may result in personal injury and or property damage In addition the object itself may fall off and cause injury and or damage Make sure th...

Страница 5: ...current power supply pressure 10 Power amplifier output 100V voltage 11 Electrical equipment electrical isolation signal input and the power output isolation in line with the 3C UL IEC60065 certifica...

Страница 6: ...turn off the power 3 NOMENCLATURE AND FUNCTIONS 3 1 FRONT PANEL T 1D120R 1D240R 1D350R 1D500R 3 2 REAR PANEL T 1D120R 1D240R 1D350R 1D500R 4 3 11 16 8 2 1 6 7 4 5 9 10 12 13 11 14 15 14 Remote Standby...

Страница 7: ...wn turn off the power NOMENCLATURE AND FUNCTIONS 3 3 FRONT PANEL T 2D120R 2D240R 2D350R 2D500R 3 4 REAR PANEL T 2D120R 2D240R 2D350R 2D500R 5 3 11 16 8 2 1 6 7 4 5 9 10 12 13 11 14 15 14 Remote Standb...

Страница 8: ...wer NOMENCLATURE AND FUNCTIONS 3 5 FRONT PANEL T 4D120R 4D240R 4D350R 4D500R 3 6 REAR PANEL T 4D120R 4D240R 4D350R 4D500R 6 3 11 16 8 2 1 6 7 4 5 9 10 12 13 11 14 15 14 Remote Standby cascading standb...

Страница 9: ...ltage range 100V speaker output 1 channels Class D amplifier output with source filters to pass invalid audio signal available for 100V external speaker The total power of the speakers connected to th...

Страница 10: ...or STBY THRU and GND are shortcut the main power amplifier will be forced off The machine will turn to standby mode with consumption less than 60W They are electrically connected in parallel you can...

Страница 11: ...d to have sufficient strength and current carrying capacity thereby ensuring under fault conditions exposed conductive parts will not lead to shock but not because of the current flowing through the p...

Страница 12: ...interference of AC power source is not so sensitive And unbalanced lines can cause noise especially when long cable through 2 Connected directly with the constant voltage speaker Speaker output line...

Страница 13: ...MODEM zero that is three wire connection And the 2nd line 3rd line is cross connect in the figure because even when direct way to communicate both look as data terminal equipment can also be sent to b...

Страница 14: ...nstructions to control the volume of data is as follows Starting bytes Channel byte Volume attenuation bytes Checksum bytes 0xFF 0x00 Channel 1 0 79dB 10dB 0x75 10dB 0x76 0x01 Channel 2 0x02 Channel 3...

Страница 15: ...8 9 10 CHIME REMOTE 2 OUTPUTS 1 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 POWER 24V 2A AUDIO OUTPUT R R L L MIC CD PLAYER PRE AMPLIFIER Volume control External standby control equipment A...

Страница 16: ...CH2 CH1 CH2 CH3 CH4 IR S2092S IR S2092S IR S 2092S IR S 2092S IR S2092S IR S2092S IR S2092S IR S2092S BP 00137 BP 00137 BP 00274 BP 00274 PA 01479 PWM PA 01479 PWM PA 01478 DC 18V BP 00137 BP 00137 B...

Страница 17: ...connect other equipments as well Pull up the power line after closing down In a sound system the amplifier should be the first to start up and the last to close down Starting up order First start up...

Страница 18: ...dB 3dB 85dB 80Hz 16kHz 10dB below maximum power 0 2 1 kHz maximum power 1 85 After a forced air into the front 50 70 Thermostat With short circuit overload over temperature protection output DC 484x44...

Страница 19: ...B 3dB 85dB 80Hz 16kHz 10dB below maximum power 0 2 1 kHz maximum power 1 85 After a forced air into the front 50 70 Thermostat With short circuit overload over temperature protection output DC 484x444...

Страница 20: ...dB 80Hz 16kHz 10dB below maximum power 0 2 1 kHz maximum power 1 85 After a forced air into the front 50 70 Thermostat With short circuit overload over temperature protection output DC 484x444 5x65mm...

Страница 21: ...37 484 POWER CH1 CH2 CH3 CH4 OFF ON PROT CLIP SIG STBY 24V DC POWER CH1 CH2 CH3 CH4 OFF ON PROT CLIP SIG STBY 24V DC 44 4 13 7 GND STBY IN GND GND STBY THRU STATE OUT CH1 CH2 CH3 CH4 100V SPEAKER OUTP...

Страница 22: ...PUBLIC ADDRESS SYSTEM VersionV0 1...

Отзывы: