ENT
PUMP CALIBRATION
060
TEST TIME
ENT to start
4.2.2 Dosing Mode
Introduce the value in the unit
and confirm with
ENT
Press to finish the calibration process
Dvol: dosed volume
Flow: flow
S.Vol: stroke volume
F.calib: calibration factor
Reduct: gearbox
ENT
PUMP CALIBRATION
PROGRESS
Strokes 076
Speed P. 0415
Max.Curr. 04,5
PUMP CALIBRATION
03,333
Dosed volume
l
PUMP CALIBRATION
DVol
03,333 l
l/h
ml
0240
22,989
100
12
SVol
FCalib.
Reduct.
Flow
The Dosing Mode function allows you to select the different Advanced Dosing
Functions. These functions can regulate the mechanism speed during the discharge
or suction cycle of the pump to optimize the dosing and adapt it to the features of
the process.
ENT
CONFIGURATION
SET UP
IN / OUT
PUMP CALIBRATION
DOSING MODE
Change with and confirm with
ENT
4.2.2.1 Standard
DOSING MODE
Mode:
Standard
Max.Flow 0240 l/h
The Stadard mode (ST) is the regular operating mode where the dosing pump
has a symmetrical behavior duringthe suction and discharge of the product.
ST
Change values with and confirm with
ENT
%
l / h
0 0 0
0 0 0
MODE
0240
20