Burner pressure tables
Note: the max heating power adjustment is allowed only in boilers classified as "range rated".
HEAT OUTPUT
Display
value
NATURAL GAS G20
BUTANE G30
PROPANE G31
kW
kcal/h
mbar
mm H
2
O
mbar
mm H
2
O
mbar
mm H
2
O
City Basic 24 C
MIN . 8 .8
7568
00
2 .2
22
4 .8
49
4 .8
49
10
8600
ê
ê
ê
ê
ê
2 .7
28
5 .9
60
6 .0
61
11
9460
3 .2
33
7 .1
72
7 .3
75
12
10320
3 .8
39
8 .3
85
8 .8
89
13
11180
4 .4
45
9 .7
99
10 .4
106
14
12040
5 .1
52
11 .1
113
12 .1
124
15
12900
5 .7
59
12 .7
129
14 .0
143
16
13760
6 .5
66
14 .3
145
16 .1
164
17
14620
7 .2
74
15 .9
163
18 .3
187
18
15480
8 .0
81
17 .7
181
20 .7
211
19
16340
8 .8
90
19 .5
199
23 .2
237
20
17200
9 .6
98
21 .5
219
25 .9
264
21
18060
10 .5
107
23 .4
239
28 .8
294
22
18920
11 .4
116
25 .5
260
31 .9
325
MAX. 23.0 19780
99
12 .3
125
27 .5
281
35 .0
357
Soft ignition
Soft ignition pressure is automatic and it needs no adjustment.
• The ignition is achieved by means of a burst of electrical sparks, while the burner is supplied with
gas, initially to the MIN pressure set on the valve gas, then pressure increases gradually (soft igni-
tion ramp) until the ignition takes place.
• The flame is detected by the flame detection electrode. When the flame is detected, the spark
burst stops, the soft ignition process terminates and the burner will be supplied with the gas
pressure corresponding to the power required by the function in progress (domestic hot water
or heating).
Electronic settings
Accessing the main board
To access the main board:
Cut off the electrical supply to the boiler.
Restore
the supply after having closed the contol panel
rear cover .
f
unscrew the screws
1
and remove the back cover of the
control panel .