14
Domestic water supply characteristics
The cold water inlet pressure must be lower than 6 Bar.
Besides, for an optimal boiler functioning, wa-
ter pressure
should be more than 1 Bar
. A lower pressure could make difficult to restore correctly the
pressure the heating system, and reduce the flow of hot water available from the boiler.
In case of higher pressure
it is indispensable to install a PRESSURE REDUCER
upstream the
boiler .
The cleaning frequency of the DHW heat exchanger depends on the water supply hardness.
If the wa-
ter hardness is more than 25° fr it’s required to install a softener to bring the hardness below that value.
Besides, the presence of solid residuals or impurities in the water (for example in case of new systems)
could compromise the correct functioning of the boiler. For DHW production systems, the regulation in
force prescribes a safety filter to protect the systems.
Protection against freezing
Thanks to its antifreeze system, inner components could never reach a temperature lower than 5°C. This
system is activated when the boiler is supplied by the electrical and gas lines, provided that the pressure
in the heating system is correct.
In case of boiler installation in rooms where temperature can drop down to 0°, it is advisable
to fill the heating circuit with an antifreeze liquid specific for heating systems, propylenic glycol
based, following the instructions of its manufacturer. Pay attention to the correct product con-
centration: adding those substances to the heating water in incorrect dose could lead to the
deformation of the seals and cause unusual noises during operation.
ITALTHERM S.r.l. will not be held responsible for consequent damages.
Instruct the User about the antifreeze function of the boiler and about the antifreeze product
added in the heating system.
Positioning and fastening
This type B boiler, with open chamber and natural draught, is not suitable for outdoor installa-
tion, neither in a partially protected place.